DEFAULT ALARM PROPERTIES
CODE
DESCRIPTION
A01
Undercompensation
A02
Overcompensation
A03
Current too low
A04
Current too high
A05
Voltage too low
A06
Voltage too high
A07
Capacitor current overload
A08
Temperature too high
A09
No-Voltage release
A10
Voltage THD too high
A11
Current THD too high
A12
Maintenance requested
A13
Step failure
NOTES: The A12 alarm is generated by the thresholds defined in P.45 and P.54 parameters. If the maintenance alarm is generated by exceeding the number of hours in the description will be present the indication HR,
if it's generated by exceeding the number of operations will be present the indication CN.
FUNCTION MENU
CODE
DESCRIPTION
F.01
Indirizzo IP
F.02
Subnet mask
F.03
Porta IP
F.04
Client/server
F.05
Indirizzo IP remoto
F.06
Porta IP remota
F.07
Indirizzo IP gatway
F.01...F.03 – TCP-IP coordinates for Ethernet interface application.
F.04 – Enabling TCP-IP connection. Server = Awaits connections from a remote client. Client = Estabilishes a connection to the remote server.
F.05...F.07 – Coordinates for the connection to the remote server when F.04 is set to client.
COMMANDS MENU
– The commands menu allows executing some occasional operations like reading peaks resetting, counters clearing, alarms reset, etc
– If the Advanced level password has been entered, then the commands menu allows executing the automatic operations useful for the device configuration
– The following table lists the functions available in the commands menu, divided by the access level required
– With controller in MAN mode, press the MODE button for 5 seconds
– Press L to select CMD
– Press AUT to access the Commands menu
– Select the desired command with MAN or AUT
– Press and hold for three seconds L if you want to execute the selected command. DCRL8 shows OK? with a countdown
– If you press and hold L until the end of the countdown the command is executed, while if you release the key before the end, the command is canceled
– To quit command menu press and hold AUT button.
CODE
COMMAND
C01
RESET MAINTENANCE
C02
RESET STEP COUNT
C03
RESET STEP TRIMMING
C04
RESET STEP HOURS
C05
RESET MAX VALUES
C06
RESET WEEKLY TPF
C07
SETUP TO DEFAULT
C08
SETUP BACKUP
C09
SETUP RESTORE
NOTES:
– The maintenance alarm A12 (maintenance hours alarm) generated by the parameter P.45 is resetted with C01 command
– The maintenance alarm A12 (maintenance operations alarm), generated by the parameter P.54, is reset before executing the C01 command and then the C02 command.
PWD. ACCESS LEVEL
DESCRIPTION
Advanced
Reset maintenance service interval.
Advanced
Reset step operation counters.
Advanced
Reload originally programmed power into step trimming.
Advanced
Reset step operation hour meters.
Advanced
Reset maximum peak values.
Advanced
Resets weekly total power factor history.
Advanced
Resets setup programming to factory default.
Advanced
Makes a backup copy of user setup parameters settings.
Advanced
Reloads setup parameters with the backup of user settings.
ENABLE
ALARM RELAY
DISCONNECTION
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
ACC
UoM
DEF
Usr
192. 168.1.1
Usr
0.0.0.0
Usr
1001
Usr
Server
Usr
0.0.0.0
Usr
1001
Usr
0.0.0.0
DELAY
15 min
120 s
G
G
5 s
B
120 s
5 s
15 min
G
180 s
G
30 s
G
0 s
G
120 s
G
120 s
0s
0s
RANGE
IP1.IP2.IP3.IP4
IP1 0...255
IP2 0...255
IP3 0...255
IP4 0...255
SUB1.SUB2.SUB3.SUB4
SUB1 0...255
SUB2 0...255
SUB3 0...255
SUB4 0...255
0...9999
Client/server
IP1.IP2.IP3.IP4
IP1 0...255
IP2 0...255
IP3 0...255
IP4 0...255
0...9999
GW1.GW2.GW3.GW4
GW1
GW2
GW3
GW4
11