MEASURES
– The DCRL8 provides a set of measurements displayed on the alphanumeric display, in conjunction with the current cosphi that is always displayed on the main display
– Press the MODE key to scroll through the measures in rotation
– After 30 seconds without pressing any buttons, the display automatically returns to the default measurement defined by P.47
– If P.47 is set on the ROT, then the measures rotate automatically every 5 seconds
– At the bottom of the list of measures it is possible to set the setpoint of the cosphi, acting on the same value set with P.19.
Below is a table with the measurements displayed.
MEASUREMENT
ICON
Delta-kvar
kvar
kvar
STEP
Voltage
V
V HI
Current
A
A HI
Weekly PF
WPF
PF
Cap. current
%C.CU
%C.HI
Temperature
°C °F
°CHI
°FHI
Voltage THD
THDV
VH02...
...VH15
Current THD
THDI
IH02...
...IH15
Cosphi setpoint
IND CAP
Step power
%
Step counter
OPC
Step hours
H
These measures are shown only if the Step trimming function is enabled (P.25=ON) and the advanced password is enabled and entered.
4
DESCRIPTION
Kvars needed to reach the cosphi setpoint. If delta-kvar is positive cpacitors need to be inserted, if negative to be disconnected.
Total kvar of the plant.
Number of equivalent steps.
RMS voltage of the plant current.
Maximum peak of measure.
RMS current of the plant voltage.
Maximum peak of measure.
Weekly average power factor.
Instantaneous total power factor.
Calculated capacitor current, in % of their nominal.
Maximum peak of measure.
Temperature of internal sensor.
Maximum peak of measure.
Total harmonic distortion % (THD) of plant voltage.
% voltage harmonic content from 2.nd up to 15.th order.
Total harmonic distortion % (THD) of plant current.
% Current harmonic content from 2.nd up to 15.th order.
Setting of desired cosphi setpoint (same as P.19).
Step residual power, as a percentage of the set rated power.
Operation counter of the step.
Hour meter of the step insertion.