Fancom MRK.2
2.2 Technical specifications
Power supply
Mains voltage
Mains frequency
Power consumption (of MRK.2)
GB: Fuse (dimensions: 5×20mm)
US and CA: Fuse (dim. 5×20mm)
Motor load
Control
Type
Feedback
Potentiometer
Limit switches
Manual control
Rotary switch
Housing
Plastic housing with screw on lid
Dimensions (l×w×h)
Weight (unpacked)
Weight model US-CA (unpacked)
Ambient climate
Operating temperature range
Storage temperature range
Relative humidity
3-phase; 230Vac/400Vac (-10% +6%)
10-0Vdc / 0-10Vdc (with EL-board)
or open-close (30Vac / 60Vdc - min. 1A)
Contact (voltage free) 30Vac / 60Vdc - min 1A
167×106×219mm (6.6×4.2×8.6 inches)
GB
2
2.2 Technical specifications
1-phase; 115Vac (-10% +6%)
1-phase; 230Vac (-10% +6%)
2×F1A - 250V
1 and 3-phase; max. 4 A
4k7 (+/- 20%)
aut.-0-open-0-close
1.45kg (3.3lbs)
0°C to +40°C (32°F to 104°F)
-10°C to 50°C (14°F to 112°F)
< 95%, uncondensed
50/60Hz
10VA
F1A - 250V
IP54
2kg (4.4lbs)