Note!
Do not touch the printed circuit or contacts!
Electrostatic charge can damage electronic
components.
(4)
(2)
(3)
Fig. 1
To fix the module mechanically, insert the four plastic clips
supplied (5) in the fixing holes (4) (Fig. 2).
(4)
(5)
Fig. 2
Affix the additional label: inputs and outputs/power supply
as in Fig. 3.
Fig. 3
To release the module, pull out the plastic clips by the
knurled knob (6) with the fingers (Fig. 4). The extension
module (1) can now be removed.
(6)
Fig. 4
6. Connections of the device
(1)
No.
Signal
30
INa
31
INb
32
–––
33
M-BUS-A
34
M-BUS-B
Attention: Do not confuse the plug-in terminals !
7. Display and operating elements
LED1
Tx
left
PWR
LED2
IN
right
Key
(1)
The key COMM serves to temporarily switch from M-Bus
to Modbus protocol, in which the physical layer of M-Bus
remains untouched.
No. 1
30 31 32 33 34
Connection
Digital input
(polarity independent)
Not to be connected
Bus connection M-BUS
(polarity independent)
Communication:
Brightness
Meaning
medium
No activity, internal
communication OK
pulsed
M-BUS telegram
dark
received
pulsed light M-BUS telegram sent
flashing
Switched to Modbus
1s/1s
protocol
dark
Internal communication
disturbed
Digital input:
Brightness
Meaning
dark
Signal inactive,
high tariff
medium
Signal active, low tariff
light
Not used
19