Brief Description; Scope Of Delivery; Technical Data; Block Diagram - Camille Bauer EMMOD206 Mode D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

1. Brief description

The extension module EMMOD206 supplements the func-
tionality and flexibility of the basic device A2xx and allows
reading instantaneous values and metering contents via M-
Bus interface. In addition a digital input is provided to syn-
chronize the intervals for the mean-values calculation or to
switch the tariff of the energy meters.
The selection of the measurements to transfer and further
settings can be performed via the keys of the basic unit. The
interface can be temporarily switched from M-Bus protocol
to Modbus protocol to allow a comfortable configuration of
the measurement functionality of the basic device A2xx by
means of the A200plus software.
The module can be retrofitted without tampering with the
basic unit. But to do so, the basic units A210, A220, A230
and A230s must be equipped with firmware version V5.0 or
higher.

2. Scope of delivery

1 Extension module EMMOD206
4 Plastic rivets
1 Operating instruction German/French/English
Additional label each for input and output/power supply

3. Technical data

Power supply
The EMMOD206 is powered by the A2xx basic unit. The
power consumption of the basic unit is increased by approx.
0.1 W when the EMMOD206 is connected.
Environmental conditions
Operating
temperature:
– 10 up to + 55 °C
Storage temperature: – 25 up to + 70 °C
Relative humidity of
annual mean:
≤ 75%
Altitude:
2000 m max.
Indoor use statement!
Communication M-Bus
Interface, protocol:
M-Bus
Baud rate:
300...38 400 baud, adjustable via
the keys of the basic unit A2xx,
auto baud is not supported.
Primary address:
0...250, adjustable via the keys of
the basic unit A2xx
Secondary
address / ID:
Is fixed and factory predefined
ID1...ID4
Corresponds to the
8-digit serial number
(sequential number) given
on the nameplate.
MAN1, MAN2 A3, 1D (GMC)
GEN
210 (for A210 and A220),
230 (for A230 and A230s)
MED
02 (Electricity)
Measurement image: Mode 1, LSB first
Mode 2 not supported
Configuration data:
non-volatile storage in the basic
unit.
ID number provided by module.
18
Collision detection:
none
Load factor bus:
0.7 (standby current approx. 1.1 mA)
Connections
Pluggable screw terminals
0.5...1.5 mm
0.5...2.5 mm
Digital input
Function
Synchronization of mean-values
or switching of high/low tariff for
energy meters
Polarity:
Any
External connection:
max. 230 V AC or DC
Passive state:
U
in
LED „IN" off
Active state:
U
in
LED „IN" on
Power consumption:
< 4 mA at 15 V DC
< 2 mA at 250 V DC
Response time:
150 ms
Galvanic isolation:
via optocoupler
Safety according EN 61010-1
Basic insulation between terminals and socket board
Rated voltage:
300 V
Measurement
category:
CATIII
Pollution degree:
2
Test voltages:
50 Hz / 1 min
2200 V: M-Bus versus basic unit
and digital input versus basic unit
3700 V: M-Bus versus digital input
Dimensions
(L x W x D) 86 x 38 x 20 mm

4. Block diagram

Rx
Tx
Tx
Rx
3.5 V
GND

5. Assembly / disassembly

The basic unit A2xx to extend must have a firmware version
5.00 or higher.
Switch-off basic unit A2xx
Simply plug-in the extension module (1) at the back of the
basic instrument (Fig. 1). Please ensure that the plug (2) and
socket (3) are aligned correctly.
2
(multiwire) or
2
(single wire)
<12 V AC/DC, high tariff
>17 V AC/DC, low tariff
Test voltage
2200 VAC
Level
Shifter
TS721
DIGIN
COMM
LED1
LED2
MBUSa
MBUSb
INa
INb

Publicité

Table des Matières
loading

Table des Matières