The series also includes "intrinsically safe" versions
[EEx ia] IIC with an intrinsically safe measurement/supply
circuit. These operate in conjunction with intrinsically safe
two-wire transmitters located in explosion hazard areas.
4. Technical data
Input signal E
1
(Input circuit between signal isolator and power pack)
DC current signal I
:
4...20 mA
E
Voltage U
:
12...30 V DC
E
≤ 50 mA continuous
Overload capacity:
Output signal A
1
(Input circuit between signal isolator and 2-wire transmitter)
DC current signal I
:
4...20 mA
A
Voltage U
(for I
= 20 mA and U
A
E
> 19.3 V
with standard (non-Ex) version,
not designed for communications protocol
> 18.5 V
with standard (non-Ex) version,
designed for FSK communication
> 14.3 V
with Ex versions,
not designed for communications protocol
> 13.3 V
with Ex versions,
designed for FSK communication
Voltage drop U
= U
– U
(at U
V
E
A
< 2.7 V
with standard (non-Ex) version,
not designed for communications protocol
< 3.5 V
with standard (non-Ex) version,
designed for FSK communication
< 7.7 V
with Ex versions,
not designed for communications protocol
< 8.7 V
with Ex versions,
designed for FSK communication
Residual ripple:
< 20 mV ss (120 kHz)
Time constant:
Approx. 5 ms
Accuracy data
< ± 0.2%
Error:
(Reference value 20 mA of output
signal, including typical linearity
error < ± 0.1%)
Ambient conditions
Commissioning
– 10 to + 40 °C
temperature:
Operating temperature: – 25 to + 40 °C, Ex – 20 to + 40 °C
– 40 to +70 °C
Storage temperature:
Annual mean
relative humidity:
75%
1
"Input" and "output" in this case refer to the direction of power
supply flow.
= 22 V):
E
) 12...22 V:
E
5. Mechanical coding of the plug-in module
Where there is a danger of inserting a module in the
wrong slot, the possibility has to be excluded as
prescribed in EN 50 020, Section 6.3.2. To this end,
the units must be supplied already equipped with
coding inserts as shown in Figures 3 and 4.
Back
A
B
C
D
E
F
G
H
I
K
L
M
Fig. 3. Coding of the plug-in
module type SI 815-61.. in
standard (non-Ex) version.
Legend to Figs. 3 and 4:
= With set of code
Back
A
B
C
D
E
F
G
H
I
K
L
M
Fig. 4. Coding of the plug-in
module type SI 815-62.. in
Ex-version, (output signal
intrinsically safe).
= Without set of code
13