1. Bus connection

The configuration of the network settings of the IEC61850 bus card of the SINEAX CAM can be performed
via one of the local interfaces by means of the CB-Manager software only.

1.1 Connection

Before a device can be connected to an existing Ethernet network, you have to ensure that it will not disturb the
normal network service. The rule is:
None of the devices to connect is allowed to have the same IP address than another device
already installed
The factory setting of the IP address of CAM is: 192.168.1.101
The standard RJ45 connector serves for the direct connection of an Ethernet cable. Previously the terminal block
for the Modbus/RTU interface must be removed. To prevent possible EMC problems the shield of the cable can
be connected to earth via the screw connector next to the Ethernet socket.
The network installation of the devices is done by means of the CB-Manager software (see chapter 1.2).
 Interface: RJ45 connector, Ethernet 100BaseTX
 Mode:
10/100 MBit/s
 Protocols: IEC 61850, NTP
LED 1 (orange)
 ON as soon as a network connection exists
 Flashing when data is transmitted via the Ethernet
connection
LED 2 (yellow)
 Flashing with 1 Hz: Start-up part 1 (boot loader)
 Flashing with 0.5Hz: Start-up part 2 (operating system and
device services)
 Flashing with 4 Hz: Start-up part 3 (start WEB server,
IEC61850 application incl. ICD parsing)
 Flashing with 10Hz: Error during start-up of IEC61850
application
 ON when ready for IEC61850 communication

1.2 Network installation by means of the CB-Manager software

The setting of the network parameters of the device may be
done via a local interface (USB and RS485). The network
settings are part of the device configuration (register
"Ethernet").
- IP address: Must be unique
- Subnet mask: Defines how many devices are directly
addressable in the network. This setting is equal for all the
devices.
- Gateway: Is used to resolve addresses during
communication between different networks
The configuration of the measurement function of the device
goes along with the setting of the network parameters.