7.5.2
Iy module
I
module
y
Direct current output for position
feedback
1 current output, terminals 61 and 62
Rated signal range
Dynamic range
Auxiliary voltage U
H
External load R
[kΩ]
B
Transmission error
Temperature influence
Resolution
Residual ripple
For connecting to circuits with the
following peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
7.5.3
SIA module
SIA module
Limit encoder with slotted initiators
and fault message output
2 slotted initiators
● Binary output (limit transmitter) A1: Terminals 41 and 42
● Binary output (limit transmitter) A2: Terminals 51 and 52
● Connection
● Signal state Low (triggered)
● 2 slotted initiators
● Function
● Connecting to circuits with the
following peak values
42
Without Ex protection/
with Ex protection Ex d
6DR4004-8J
+12 ... +35 V
-
-
Safe galvanic isolation from alarm option and basic device
Without Ex protection
6DR4004-8G
2 wire technology in accordance with EN 60947-5-6 (NAMUR), for switching
Nominal voltage 8 V;
current consumption:
≥ 3 mA (limit not
activated),
≤ 1 mA (limit activated)
With Ex protection Ex ia
(only in temperature class
T4)
6DR4004-6J
2-wire connection
4 ... 20 mA, short-circuit proof
3.6 ... 20.5 mA
+12 ... +30 V
≤ (U
[V] - 12 V)/i [mA]
H
≤ 0.3%
≤ 0.1%/10 K (≤ 0.1%/18 °F)
≤ 0.1%
≤ 1 %
U
= DC 30 V
i
I
= 100 mA
i
P
= 1 W
i
C
= 11 nF
i
L
= negligibly small
i
DC 840 V, 1 s
With Ex protection Ex "ia"
6DR4004-6G
2-wire connection
amplifiers connected on load side
< 1.2 mA
Type SJ2-SN
NC contact (NC, normally closed)
U
= DC 15 V
i
I
= 25 mA
i
P
= 64 mW
i
With Ex protection
Ex "ic", "nA", "t"
6DR4004-6J
+12 ... +30 V
"ic":
U
= DC 30 V
i
I
= 100 mA
i
"nA"/"t":
U
≤ DC 30 V
n
I
≤ 100 mA
n
P
≤ 1 W
n
C
= 11 nF
i
L
= negligibly small
i
With Ex protection Ex "ic",
"nA", "t"
6DR4004-6G
"ic":
U
= DC 15 V
i
I
= 25 mA
i
"nA":
U
≤ DC 15 V
n
P
≤ 64 mW
n
SIPART PS2 (6DR5...)
A5E03436620-04, 02/2014