11- Features
•
Dimensions (height-width-depth)
•
Material
•
Working temperature
GB
•
Relative humidity
•
Protection index
•
Conditions of class type
•
Models:
•
Maximum number of elements per zone
•
Output voltage per zone
•
Maximum current per zone
•
Maximum length of the zone line
•
Maximum capacity of the zone line
•
Recommended cable
•
Maximum resistance of the zone line
•
End of line resistor of the zone
•
Voltage-free relay
•
Contact rating
•
Voltage/free relay
•
Contact rating
•
Quiescent status
Mechanical features
Environmental features
Maximum 95% no /condensing
Zones features
Minimum 18 Vdc Maximum 29 Vdc
Alarm relay features
1 relay with C, NO, NC contacts
Fault relay features
1 relay with C, NO, NC contacts
30
439 mm x 268 mm x 112 mm
ABS
Between –5 ºC y 40 ºC
IP30
3K5 de la EN60721-3-3-1995
2 zones
4 zones
8 zones
12 zones
32 detectors or 32 MCP
84 mA
2 Km
500 nF
Twisted de 2 x 1,5 mm
44 Ohmios
4K7 Ohmios 1/4W
2A a 30 Vdc
2A a 30 Vdc
Energised
2