7- Maintenance
The following does not replace the care recommendations of EN54-14.
7.1- 5.1- User maintenance
The user must make daily and monthly checks:
•
The user must check daily as follows: The panel must indicate normal operation. If
faults are recorded in the event log, advise the company responsible for maintaining
GB
the equipment.
•
The user must check each month: The state of the installation by triggering a
detector or call point. A different zone should be tested every month. Any anomaly
detected in these tests shall be recorded in the logbook of incidents, taking corrective
action as soon as possible.
7.2- Maintainer maintenance
The maintenance and installation companies must make quarterly and annual checks:
•
The company in charge of maintenance of the facility shall test every six months as
follows:
»
Check the entries in the logbook of incidents, carrying out the necessary corrective
actions.
»
Examine the battery connections and load voltage.
»
In each zone, check the functions of alarm, fault and auxiliary equipment.
»
Visually inspect the equipment to detect any increase in moisture or any other
deterioration.
»
Find out if there has been some structural changes at the facility, which could alter
the normal operation of the facility
•
The company responsible for maintenance of the facility must demonstrate annually
that:
»
Put the panel into test mode, and verify that all sensors and call points operate
according to the manufacturer's specifications.
»
Inspect all connections to the panel and its attachment to verify that there has been
no deterioration.
»
Examine the state of the batteries and replace if necessary.
»
We recommend replacing the batteries every 4 years, even if they are OK.
26