The conventional panels have two 24V auxiliary outputs, one of which is resettable.
The total current of the 2 outputs is 500 mA and is protected by a common fuse.
4.4.1- 24V auxiliary output connector
The 24Vdc outputs are intended to supply voltage to the external auxiliary elements
that need a power supply; we do not recommend you use this output to supply elements
that have consumption when on standby.
4.4.2- Resettable 24V auxiliar output conector
The resettable 24Vdc output is for supplying devices that need to be reset from the
panel (like beam detector). This output has 24V on standby and, when the panel is
reset, the 24V are disconnected for 3 seconds.
4.5- Free relay output connector
The panel has a fault relay and an alarm relay for outputs that act as an alarm or
malfunction. The maximum relay contact current is 2A.
The fault relay is energised, thus will switch if a fault occurs, indicating the corresponding
fault.
4.4- 24V output connector