11. Inspect the tank heater regulator to ensure it is not damaged or the vent is not blocked.  Make sure it 
is mounted above the vapor space of the tank.   
 
12. After connecting to the battery, check the voltage inside the preheater cable connection 
box to ensure it is 11 Volts DC or greater. 
 
13. Voltage of  the Peltier device, measured between terminal 3  and 5, should be  90 mV or 
higher to start  the heater pilot and when the heater  is  warm  and operating  this should 
measure 300‐400 mV (visit troubleshooting information in Section 5). 
 
14. Manifold gas pressure should be according to the table in Figure 8.  See Figure 3 for gas port location. 
 
15. The temperature of the heater face should be 750 – 822 °F (399 – 439 °C). If the heater surface does not 
reach full  temperature after an hour of operation 750 °F (399 °C) and tank pressure is less than 55 psi 
(3.8 bar), contact the  factory for instructions (see the following page). 
Pilot Mode 200 – 300 mV                                              Full Heat Mode 300 – 425 mV 
                                           
 
 
ASDI Operations and Maintenance – Second Sun – P/N 52793 
 
  Fig. 16                                                                                 Fig. 17 
 
 