Electrical Installation; Wiring Guidelines - Franklin Electric MONODRIVE UTILITY Manuel Du Propriétaire

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

INSTALLATION AND SETUP

Electrical Installation

Electrical Installation

Wiring Guidelines

Follow the recommendations in this section to ensure best performance of the MonoDrive Utility
and to avoid interference with other devices.
Cable Routing
Use the above diagram as a guide when routing wiring to the VFD.
1. Mount the drive as close as possible to the service entrance panel. Wire directly to the service
entrance. Do not connect to a sub-panel.
2. Use a dedicated branch circuit for the drive. Refer to
page
17.
3. Route motor wiring out of building as soon as possible. Separate input power and motor wir-
ing by at least 8 in. (20.3 cm). Refer to
4. Cross over other branch circuits and facility wiring at a 90 angle. If it is necessary to run wir-
ing in parallel, separate by at least 8 in. (20.3 cm).
All control wiring—sensors, switches, transducers, etc.—should be in a separate conduit routed
individually, not parallel, from high voltage wiring. In addition, any shielded cables should be prop-
erly grounded.
16
"Fuse/Circuit Breaker and Wire Sizing" on
"Maximum Motor Cable Length" on page
17.

Publicité

Table des Matières
loading

Table des Matières