Operation (contd.)
AUXILIARY (AUX)
When this light is on it indicates the remote switch
contacts are closed. This allows you to observe if
your remote switch is properly closing the heater
control circuit. When shipped from the factory a
jumper is installed to maintain closed circuit in the
absence of a remote switch.
PRESSURE (PRESS)
This light is on when Spa/Pool Selector switch is
on, indicates the circulation pump is running prop-
erly. If pressure light fails to light, the pump may
have lost its prime or water flow may be restricted
by an inadvertently closed valve or clogged filter or
pump basket. If you have determined that there is no
water flow restriction to the heater, you should call
a qualified serviceman.

TROUBLESHOOTING (CONTROLS)

Example of troubleshooting with the assistance of the indicator lights.
INCOMING
LINE VOLTAGE
THERM
AUX
PRESS
HEAT
INCOMING
LINE VOLTAGE
THERM
AUX
PRESS
HEAT
Rev. K 5-31-06
LED OFF
LED LIT
TRANSFORMER
CIRCUIT
REMOTE
BREAKER
THERMOSTAT
RELAY
PWR
TSTAT
POWER
SERVICE
WATER AT SELECTED TEMPERATURE.... NORMAL OPERATION
OR POOL/OFF/SPA THERMOSTAT SELECT SWITCH OFF.... NORMAL OPERATION
FRONT PANEL LEDS
TRANSFORMER
CIRCUIT
REMOTE
BREAKER
THERMOSTAT
RELAY
PWR
TSTAT
POWER
SERVICE
THERMOSTAT CALLING FOR HEAT - PUMP OFF(NO PRESSURE) BLOCKS FIRING
NORMAL OPERATION
FRONT PANEL LEDS
HEAT (HEAT)
The heat light is on any time the thermostat has
signaled a call for heat which initializes the ignition
safety firing circuit -- the light comes on to indicate
successful firing of the main burners.
SERVICE (SERVICE)
The service light is off during normal operation of
heater. The light only comes on if a problem with a
control has occurred or when the heater is first
firing. The problem must be investigated by the
serviceman prior to attempts to fire the heater again.
The diagrams that follow give examples of
troubleshooting a malfunctioning heater using the
assistance of the indicator lights.
SYMBOL TABLE
SWITCH OR DEVICE
SWITCH OR DEVICE
OPEN CIRCUIT
CLOSED CIRCUIT
(BLOCK CURRENT)
(PASS CURRENT)
IND
HI TEMP
PRESS
TFUSE
LIMIT SWITCHES
RMT
PRESS
HI TEMP
TFUSE
SRVE
CLOSE IF
NO MV
THERMOSTAT CIRCUIT BOARD
IND
HI TEMP
PRESS
TFUSE
LIMIT SWITCHES
RMT
PRESS
HI TEMP
TFUSE
SRVE
CLOSE IF
NO MV
THERMOSTAT CIRCUIT BOARD
IGNITION MODULE
GND
VAL
GAS VALVE
MV
MV
MV
HEAT
IGNITION MODULE
GND
VAL
GAS VALVE
MV
MV
MV
HEAT