MiniMax CSD-1 Controls (contd.)
2 8
LOCKOUT CONTROL
The lockout control provides continuity for a 24vac pool heater
control circuit. A contact closure provided by the heater system
ignition controls operates a latching relay removing continuity from
the heater control circuit. Continuity will remain removed until a
manual reset button on the control board is operated. A board
mounted LED indicates the control status. The Lockout State will
be retained through power outage.
LOW WATER CUT OFF
The low water cut off automatically shuts down burner system
whenever water level drops below probe. Minimum clearance
from probe to any surface within the heater or tee is ¼ in.
HI LIMIT CONTROL
The pool heater is equipped with a manual reset High Limit, push
the reset button and set the High Limit to 40° F. above the desired
operating temperature. Maximum temperature setting is 160° F.
A-4
P/N 470880
Rev. K 5-31-06