TECHNICAL DATA
Thermal power
Fuel
Max. gas pressure
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
One stage operation
Absorbed electrical power
For gas family 3 (LPG) ask for separate kit.
GAS CATEGORY: II2H3B/P.
Burner for applications not provided for in Article 1 – Paragraph 1 of Directive 90/396/EEC.
The burner meets protection level of IP 40, EN 60529.
Burner in conformity with Directive: Electromagnetic Compatibility 2004/108/EC and Machine
Directive 2006/42/EC.
– Suction line
1
– Return line
2
– Vacuum gauge connection
3
– Gauge connection
4
– Pump pressure regulator
5
– Terminal board
6
– Air pressure switch
7
– Delivery tube
8
2127
80 197 kW
–
Light oil, max. viscosity at 20 °C: 6 mm
Natural gas Pci 8 12 kWh/m
35 mbar
Single phase, 230V ± 10%
230V / 1.4A
5 F
Primary 230V / 1.9A - Secondary 2 x 5 kV 30 mA
Output 30 kg/h to 10 bar - Max. pressure 15 bar
Full flow light oil ignition
Stand-by rate gas ignition
0.32 kW
Fig. 1
S7356
9 – UV photocell
10 – Lock-out lamp and reset button
11 – Grommet
12 – Selector switch
13 – Air damper
14 – Gas pressure test point at sleeve
15 – Screws fixing air-damper
16 – Filter
1
GB
68,000 170,000 kcal/h
2
/s (1.5 °E)
3
– 7,000 10,340 kcal/m
~
50Hz
3