OPERATION
Air bleed: through the screw provided on the gas pressure switch

COMBUSTION CHECK

CO
2
It is essential to adjust the burner with a CO
By doing so, a small miscalibration (for instance a change in draft) can not cause combustion with air
deficiency and consequent formation of CO.
CO - It must not be higher than 100 mg/kWh (93 ppm) in compliance with EN 676.
It is important to take into account that the fan air output var-
ies according to whether the burner's cover is fitted or not.
Proceed as follows:
– adjust the air damper;
– fir the cover and check the bacharach values (CO
– if necessary, change the air flow, remove the cover, adjust the
gate valve, refit and check the values again.
NOTE: When the burner runs with an output higher than 188
kW (160,000 kcal/h), remove the panel fitted within the
cover (see figure on the right).

START-UP CYCLE

Thermostat
Motor
Ignition transformer
Valve (oil - gas)
Flame
Lock-out lamp
If the flame goes out during operation, a lock-out takes place within 1 second.
2127
Screw
Connection for pressure
measurement
Air pressure switch
2
Normal
1s
3s max.
30s min.
GAS PRESSURE SWITCH
For any adjustment see the instructions for
the gas train.
AIR PRESSURE SWITCH (7, fig. 1)
(factory-set at 0.5 mbar).
not higher than 10% c.a. (gas with Pci 8600 kcal/m
- CO);
2
Lock-out, due to light-failure
10 GB
PANEL
S7362
1s
3s max.
30s min.
3
).
D5840