LINE OF GAS-SUPPLY
– Gas supply pipe
1
– Manual cock (charged to the installer)
2
– Gas pressure gauge (charged to the installer)
3
– Filter
4
– Gas pressure switch
5
– Safety valve
6
RAMPA GAS
MULTIBLOC
Gas train
Rp 3/4
MBDLE 407 B01
Rp 3/4
MBDLE 410 B01
The gas train is supplied separately, for its adjustment see the enclosed instructions .
THE BURNER IS SET TO WORK WITH TWO KINDS OF FUEL:
Switching from one fuel to the other is done by turning the selector (12) to the desired position .
LIGHT OIL OPERATION ( see figure below )
Turn the selector switch (12) to OIL.
By doing so, the gas pressure switch is short-circuited and the unit can run without any gas in the sys-
tem. The gas valves are de-energised and gas is prevented from passing through. When the control
box sends the signal, the oil valve (1) is energised. If the unit is to run on light oil for a long time, it is
recommended that the manual gate in the gas delivery pipe be closed.
GAS OPERATION
Turn the selector switch (12) to GAS.
The gas pressure switch is reset and the burner works only
with an adequate gas pressure. When the control box sends
the signal, the gas valve is energised. The valve (1) stays
de-energised and light oil is prevented from passing
through.
Important
There must be light oil in the tank and the pump must be
primed even if the burner is running on gas. If there were no
fuel in the tank, the pump would seize. If there is no light oil,
the motor-pump coupling (3) must be removed. This is rec-
ommended also if the burner runs on gas for a long time.
2127
1
2
3
Connection
Burner
Rp 3/4
Natural gas and LPG
Rp 3/4
Natural gas and LPG
LIGHT OIL AND NATURAL GAS
M1
4
5
6
– Pressure governor
7
st
– 1
8
M1 – Gas-supply pressure test point
M2 – Pressure coupling test point
ALTERNATIVELY RIELLO GAS TRAIN
Employ
DUNGS GF 507/1 filter
DUNGS FRS 207/1 stabiliser
DUNGS GW 50 A4 pressostat
Riello valve (R.B.L.) 487SE e 488SE
5
GB
7
8
M2
nd
and 2
stage adjusting valve
WITH:
D5069
S7363