7.2 Service Level - REMEHA c-Mix Notice D'installation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

#
brief description
Pump choice
3
group 1
Pump choice
4
group 2
5
Group priority
6
Controllers
7
Sensors
#
brief description
21
Hot water start
22
Hot water stop
Hot water
23
overtemperature
Central heating
24
overtemperature
Requested hot
28
water temp
long description
Choices
Automatic
3: Pump choice
No post-circulation time
group 1.
Post-circulation time 1 minute
Can also be set
Post-circulation time 10 minutes
using rotary switch
Continuous post-circulation
Automatic
4: Pump choice
No post-circulation time
group 2.
Post-circulation time 1 minute
Can also be set
Post-circulation time 10 minutes
using rotary switch
Continuous post-circulation
5: Choice of group
Priority to group 1
priority. Also via
Priority to group 2
rotary switch
No priority
No OpenTherm controllers
6: Connected
On connection 1
OpenTherm
On connections 1 and 2
controllers
On connection 1 (2 groups)
On 1 (2 groups) and on 2
Toutside=No, T1=No, T2=No
Toutside=Yes, T1=No, T2=No
Toutside=No, T1=Yes, T2=No
7: Connected
Toutside=Yes, T1=Yes, T2=No
temperature
Toutside=No, T1=No, T2=Yes
sensors
Toutside=Yes, T1=No, T2=Yes
Toutside=No, T1=Yes,T2=Yes
Toutside=Yes, T1=Yes, T2=Yes
long description
21: The hot water group heats the calori-
fier when the measured hot water
temperature falls below the required hot
water temperature minus this value
22: The hot water group stops hea-
ting the calorifier when the measured
hot water temperature rises above the
required hot water temperature plus this
value
23: The hot water group heats the calo-
rifier with a temperature that equals the
required hot water temperature plus this
value
24: The requested central heating tempe-
rature is slowly increased up to this
value when the valve is fully open
and the temperature has not yet been
reached.
28: Standard value for the requested hot
water temperature
46
Remeha
Standard value
Automatic
Automatic
No priority
No OpenTherm controllers

7.2 Service level

Choices
0..40°C
0..20°C
0..30°C
0..20°C
30..70°C
c-Mix
Standard value
5
5
10
20
60