4.7.4
The 'Save config' button is used to save the
selected configuration on the
This can take up to one minute.
4.7.5
If one
nection G. If several
boiler or the 'previous'
here (see paragraph 4.3.8 and 4.7.11).
4.7.6
Type of control
2 weather-compensated
control groups
2 room control groups
1 weather-compensated
control group, 1 room con-
trol group
A controller is connected to connection 1. If sev-
eral Cmix modules are being used, the 'next'
module is connected (see paragraph 4.3.7 and 4.7.11)
4.7.7
The required sensors are connected to the follow-
ing connections:
- J. (Tout): Outside sensor
- K. (T1): Mixing group 1 contact sensor
- L. (T2): Mixing group 2 contact sensor or storage tank sensor
Sensor status led
Signal
On
Flashes 2 x per second
Flashes 4 x per second
location of the sensor
Outside sensor
Contact sensor
Storage tank
sensor
T001043-06-B
39
'Save config' button (F)
c-Mix
Boiler connection or 'previous' c-Mix (OTm) (G)
is used, the boiler is connected to con-
c-Mix
modules are used, the
c-Mix
module is connected
c-Mix
Controller connections (OT1 and OT2) (H
and I)
Quantity and type of sensors
2 OpenTherm controllers (with
weather-compensated control)
or 1 Remeha iSense controller
2 OpenTherm controllers or 2
Remeha iSense controllers
2 OpenTherm controllers (with
weather-compensated control)
or 1 Remeha iSense controller
Sensor connections (Tout, T1 and T2)
(J, K and L)
Status
Sensor connected and active
Fault
Configuration is detected
•
Install the outside sensor so that
it is shielded from direct sunlight.
•
The sensor must be positioned
at least 2.5 metres above ground
level.
•
Do not install the outside sensor
near windows, doors, ventilation
grills or extractors, etc.
Fit the contact sensor to the mixing group
flow.
Fit the storage tank sensor in the calorifier.
.
c-Mix