NO
1
2
prio
A
8
8
B
8
8
T002653-B
Remeha
4.7.8
Rotary switches for setting pumps 1 and 2 (O)
Position
Setting
0
Temperature-controlled post-circulation time (for
optimum use of the residual heat)
1
Post-circulation time 0 min.
2
Post-circulation time 1 min.
3
Post-circulation time 10 min.
4
Pump runs continuously
Select a post-circulation time of 0 minutes if no
valve is used.The group pump is switched when
the group has a heat demand. The post-circula-
tion time can be set. No post-circulation time: As
soon as there is no longer heat demand, the group
pump is switched off. Use this setting if no valves
are used.
Continuous: The group pump runs continuously.
Automatic: The groups pump post-circulation time
depends on the temperature decrease measured
by the group contact sensor. The post-circulation
time is at least 3 minutes and at most 30 minutes.
Pump status led
Signal
On
Off
4.7.9
Rotary switches for setting valves 1 and 2 (P)
Position Setting
0
Closed manually (only for test purposes)
1
Opened manually (only for test purposes)
2
Thermal valve (2 contacts with 2-way valve)
3
Thermal valve (2 contacts with 3-way valve)
Open-closed valve (2 contacts with 2-way valve),
4
running time 0..30 s.
Open-closed valve (2 contacts with 2-way valve),
5
running time 30 s..2 min.
Open-closed valve (2 contacts with 2-way valve),
6
running time 2..4 min.
Mixing valve (2 contacts with 3-way valve),
7
running time 0..30 s.
Mixing valve (2 contacts with 3-way valve),
8
running time 30 s..2 min.
Mixing valve (2 contacts with 3-way valve),
9
running time 2..4 min.
Mixing valve (3 contacts with 3-way valve),
A
running time 0..30 s.
Mixing valve (3 contacts with 3-way valve),
B
running time 30 s..1 min.
Mixing valve (3 contacts with 3-way valve),
C
running time 1..2 min.
Mixing valve (3 contacts with 3-way valve),
D
running time 2..4 min.
E
Not in use
Group 1: DHW eco relay (pump switches off when
F
DHW standby function is switched off)
Group 2: calorifier group
40
c-Mix
Status
Pomp is active.
Pomp is not active.