Symbols In The Document; Intended Use - SMA SUNNY TRIPOWER 8.0 Notice

Masquer les pouces Voir aussi pour SUNNY TRIPOWER 8.0:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 63
SMA Solar Technology AG
Indicates a situation which, if not avoided, can result in property damage.
1.5

Symbols in the Document

Symbol
Explanation
Information that is important for a specific topic or goal, but is not safety-rele-
vant
Section in which the installation and commissioning process is illustrated
graphically.
2
Safety
2.1

Intended Use

The Sunny Tripower is a transformerless PV inverter which converts the direct current of the PV array
to grid-compliant three-phase current and feeds it into the utility grid.
The product is suitable for indoor and outdoor use.
The product must only be operated with PV modules of protection class II in accordance with
IEC 61730, application class A. The PV modules must be compatible with this product.
The product is not equipped with a transformer and therefore has no galvanic isolation. The
product must not be operated with PV modules whose outputs are grounded. This can cause the
product to be destroyed. The product may be operated with PV modules whose frame is grounded.
PV modules with a high capacity to ground must only be used if their coupling capacity does not
exceed 3.75 µF (for information on how to calculate the coupling capacity, see the Technical
Information "Leading Leakage Currents" at www.SMA-Solar.com).
PV modules with a high capacity to ground must only be used if their coupling capacity does not
exceed 3.75 µF (for information on how to calculate the coupling capacity, see the Technical
Information "Leading Leakage Currents" at www.SMA-Solar.com).
All components must remain within their permitted operating ranges and their installation
requirements at all times.
The product must only be used in countries for which it is approved or released by SMA Solar
Technology AG and the grid operator.
Use this product only in accordance with the information provided in the enclosed documentation
and with the locally applicable laws, regulations, standards and directives. Any other application
may cause personal injury or property damage.
Alterations to the product, e.g. changes or modifications, are only permitted with the express written
permission of SMA Solar Technology AG. Unauthorized alterations will void guarantee and
warranty claims and in most cases terminate the operating license. SMA Solar Technology AG
shall not be held liable for any damage caused by such changes.
Quick Reference Guide
NOTICE
STP8-10-3AV-40-IS-xx-11
2 Safety
5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sunny tripower 10.0Stp8.0-3av-40Stp10.0-3av-40

Table des Matières