Seasonal Wind And Cautions In Winter - Friedrich MR24DY3JMA Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Seasonal Wind And Cautions In Winter

- Sufficient measures are required in a snow area or severe cold area in winter so that product can
be operated well.
- Get ready for seasonal wind or snow in winter even in other areas.
- Install a suction and discharge duct not to let in snow or rain.
- Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the
air suction hole, the system may malfunction. If it is installed at snowy area, attach the hood to the
system.
- Install the outdoor unit at the higher installation console by 50cm than the average snowfall (annual
average snowfall) if it is installed at the area with much snowfall.
- Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always re-
move snow for operation.
1. The height of H frame must be more than 2 times the snowfall and its width shall not exceed the
width of the product. (If width of the frame is wider than that of the product, snow may accumulate)
2. Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal wind.
Installation of Indoor, Outdoor Unit
Installation Manual 11

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Mr36tqy3jmaMr49dey3jm

Table des Matières