CLIMATIC™ 60 – REFROIDISSEURS DE LIQUIDE A CONDENSATION PAR AIR
Level 1
Item
Level 2 Item
Expert
Unit
Expert
Unit
Expert
Unit
Expert
Unit
Expert
Unit
Expert
Unit
Expert
Unit
Expert
3200
Water
Expert
Water
Expert
Water
Expert
Water
Expert
Water
Expert
Water
Expert
Water
Expert
Water
Expert
Water
Expert
Water
Expert
Water
Expert
Water
Expert
Water
Expert
Water
Page 60
Level 3 Item
Level 4 Item
3160
Option
3161
Pump Cool
Option
3162
Pump Heat
Option
3163
FP Cos
Option
3164
Freecooling
Option
3165
Power meter
Option
3166
Heater Elec
Option
3167
Remote DC
3210
Temperature
3211
Inlet
Temperature
3212
Inlet Ref
Temperature
3213
Outlet
Temperature
3214
Outlet Ref
Temperature
3215
Delta T°
Temperature
3216
Setpoint
Temperature
3217
Capacity
Temperature
3218
Flow
3220
Changeover
3221
Status
Changeover
3222
Outside
Changeover
3223
Outside Ref
Changeover
3224
Mode
Changeover
3225
Winter
Changeover
3226
Summer
R/W/Z
Unit
Min
Std
0=Not Set,
R/W
*
1=Single=,
2=Single%,
0=Not Set,
R/W
*
1=Single=,
2=Single%,
R/W
*
0=No, 1=Yes.
R/W
*
0=No, 1=Yes.
0=Not Set,
1=1,.,.,
R/W
*
2=.,2,.,
3=1,2,.,.
R/W
*
0=No, 1=Yes.
R/W
*
0=No, 1=Yes.
R
°C
-50,0
R
°C
-50,0
R
°C
-50,0
R
°C
-50,0
R
°C
-50,0
R
°C
-50,0
R
%
-50,0
R
*
0
R
*
*
R
°C
-50,0
R
°C
-50,0
0=Not Used,
R/W/Z
*
1=Cool,
2=Heat,
R/W
°C
-10,0
18,0
R/W
°C
19,0
23,0
Max
Description
3=Double=,
Evaporator pump(s)
4=Double%.
configuration
3=Double=,
Condenser pump(s)
4=Double%.
configuration
Power factor correction
configuration
Freecooling configuration
Power meter configuration
Electrical heater configuration
Remote DC60 configuration
*
105,0
Evaporator inlet probe T°
*
105,0
Evaporator inlet reference T°
*
105,0
Evaporator outlet probe T°
*
105,0
Evaporator outlet reference T°
Evaporator delta T° (Inlet-
*
105,0
Outlet)
*
105,0
Evaporator set point
*
105,0
Evaporator capacity
*
1
Evaporator flow switch
*
*
Changeover status
*
105,0
Outside air probe T°
*
105,0
Outside air reference T°
3=Auto,
Changeover mode
4=Dead zone.
Winter T° to swap in heating
30,0
mode
Summer T° to swap in cooling
30,0
mode
MUL41F-0610/06-2011