9.8 - CONNECTING THE 230 V LIGHT OUTPUT*
To perform the connection see Fig. 32 and consult the relevant instruction
manual.
* Not present in:
FILO400SP/AU01 - FILO400ST/AU01 - FILO600SP/AU01 - FILO600ST/AU01
9.9 - INSTALLING THE EXTERNAL RELEASE SYSTEM model KS200KIT
To install the KS200KIT external release system in the gearmotor, see Fig. 33 and consult the relevant instruction manual.
01.
33
2
1
04.
2
9.10 - DIAGNOSTICS AND DEVICE SIGNALS
Certain devices are configured to display messages to identify their operating status or any anomalies.
9.10.1 - Photocell signals
The photocells contain a SAFE led (Fig. 6/A) that allows for verifying their operating status at any time: see Table 7.
SAFE led (Fig. 6/A)
Status
Off
The photocell is not powered or is
faulty
3 quick flashes and 1
Device not recognised by the control
second pause
unit
1 very slow flash
The RX receives an excellent signal
1 slow flash
The RX receives a good signal
1 quick flash
The RX receives a poor signal
1 extremely fast flash
The RX receives a bad signal
Always lit
The RX does not receive any signal
02.
1
2
1
3
Action
Check that the voltage on the photocell terminals is around 8–12 VDC; if the volta-
ge is correct, the photocell is probably faulty
Repeat the recognition procedure on the control unit. Check that all pairs of pho-
tocells on the ECSBus have different addresses (consult the instruction manual of
the photocells)
Normal operation
Normal operation
Normal operation but check TX-RX alignment and correct cleaning of photocell lenses
At the limit of normal operation; check TX-RX alignment and correct cleaning of
photocell lenses
Check for any obstruction between TX and RX. Check that the Led on TX emits a
slow flash. Check the TX-RX alignment