NOTE:
If any probe other than the PosiTector DPM probe is
attached to the PosiTector Advanced body while connected to
a PosiTector CMM IS probe, the gage body will ignore the
attached probe and only display the PosiTector CMM IS
measurements.
Recorded measurement values can be reported using PosiSoft
Solutions. See the PosiTector DPM Instruction Manual for more
information.
Step 6 – Remove the PosiTector CMM IS Probes
The PosiTector CMM IS probes are designed to be reusable.
Once measurements are complete, use the extraction tool to
remove the probes from the holes. Clean any visible debris or
concrete dust from the probes and inspect the silicone fins. If the
silicone fins are damaged or worn, they should be replaced. If no
further tests are required, remove the batteries by unscrewing the
battery covers and pushing the battery out using the probe
extraction tool and place each probe into a Calibration Check
Chambers for storage.
Once testing is complete, the holes should be filled with a
cementitious patching compound in accordance with ASTM
F2170.
Specifications
Temperature
Humidity
* 0 – 65 ˚ C (32 – 150 ˚ F)
Range
0˚ to 80˚ C
32˚ to 175˚ F
10 to 90%
> 90%
12
Accuracy
± 0.5˚ C
± 1˚ F
± 2%*
± 3%*
Resolution
0.1˚ C
0.1˚ F
0.1%