Emerson AVENTICS IO-Link AF2 Notice D'instruction page 12

Capteur de débit
Masquer les pouces Voir aussi pour AVENTICS IO-Link AF2:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14
AVENTICS specific
448
Low flow cut-off
Float
(0x1C0)
input
449
Input smoothing
UInt
(0x1C1)
filter for flow
450
Flow measuring
UInt
(0x1C2)
mode
453
Input zero point
Float
(0x1C5)
offset for pres-
sure
454
Input smoothing
UInt
(0x1C6)
filter for pressure
458
Input smoothing
UInt
(0x1CA)
filter for temper-
ature
481
Signal quality 1
UInt
(0x1E1)
(sensor robust-
ness)
482
Signal quality 2
UInt
(0x1E2)
483
Signal quality 3
UInt
(0x1E3)
484
Signal quality 4
UInt
(0x1E4)
485
PowerUp
UInt
(0x1E5)
counter
486
Power supply
Float
(0x1E6)
sensor
487
Sensor
Float
(0x1E7)
temperature
488
Mass flow
Record
(0x1E8)
statistics
1 (0x01)
Minimum
Bit (64)
2 (0x02)
Maximum
Bit (32)
3 (0x03)
Average value
Bit (0)
489
Flow speed
Record
(0x1E9)
statistics
490
Volume flow
Record
(0x1EA)
statistics
491
Temperature
Record
(0x1EB)
statistics
492
Pressure
Record
(0x1EC)
statistics
493
Statistics dura-
UInt
(0x1ED)
tion since reset
496
Counter status
UInt
(0x1F0)
since reset
502
Active messages Record
(0x1F6)
1 (0x01)
Message 1
Bit
number
(1104)
AVENTICS™ IO-Link AF2 | R412027828-BAL-001-AA | English
4
rw 0.0 ... 10.0
bytes
8 bits
rw 0 = off
1 = 100ms
2 = 200ms
5 = 500ms
10 = 1sec
20 = 2sec
50 = 5sec
100 = 10sec
8 bits
rw 0 = standard
4
rw -0.5 ... 0.5
[bar]
bytes
8 bits
rw 0 = off
1 = 100ms
2 = 200ms
5 = 500ms
10 = 1sec
20 = 2sec
50 = 5sec
100 = 10sec
8 bits
rw 0 = off
1 = 100ms
2 = 200ms
5 = 500ms
10 = 1sec
20 = 2sec
50 = 5sec
100 = 10sec
8 bits
ro
0 ... 100
[%]
8 bits
ro
0 ... 100
[%]
8 bits
ro
0 ... 100
[%]
8 bits
ro
0 ... 100
[%]
32 bits ro
4
ro
[V]
bytes
4
ro
(Parameter in 0.1°C) [°C]
bytes
12
ro
bytes
4
ro
bytes
4
ro
bytes
4
ro
bytes
12
ro
See index 488
bytes
12
ro
See index 488
bytes
12
ro
See index 488
bytes
12
ro
See index 488
bytes
32 bits ro
See index 488
32 bits ro
Reset process data rVolume, rMass,
rEnergy
140
ro
4 active messages with highest prior-
bytes
ity
16 bits ro
AVENTICS specific
2 (0x02)
Message 1 level
Bit
(1096)
3 (0x03)
Message 1
Bit (840) 32
description
4 (0x04)
Message 2
Bit (824) 16 bits ro
number
5 (0x05)
Message 2 level
Bit (816) 8 bits
6 (0x06)
Message 2
Bit (560) 32
description
7 (0x07)
Message 3
Bit (544) 16 bits ro
number
8 (0x08)
Message 3 level
Bit (536) 8 bits
9 (0x09)
Message 3
Bit (280) 32
description
10 (0x0A) Message 4
Bit (264) 16 bits ro
number
11 (0x0B) Message 4 level
Bit (256) 8 bits
12 (0x0C) Message 4
Bit (0)
description
17342
Hardware identi-
String
(0x43BE)
fication key
ro = read only, rw = read/write
Standard command
2 (0x02)
Standard
wo
command
wo = write only
8 bits
ro
0 = no message
1 = information
2 = warning
3 = error
ro
bytes
ro
0 = no message
1 = information
2 = warning
3 = error
ro
bytes
ro
0 = no message
1 = information
2 = warning
3 = error
ro
bytes
ro
0 = no message
1 = information
2 = warning
3 = error
32
ro
bytes
32
ro
bytes
83
BM_ACTIVATE
128
Reset device
130
Restore state on delivery
210
Reset all statistics values
211
Reset all counter values
12

Publicité

Table des Matières
loading

Table des Matières