Panel Mounting
Mounting Guidelines
• For Indoor Use Only! NEMA, Type 1 enclosure,
IP20.
• Panel generates heat. Mount only where ambient
temperature is 32 to 104 °F (0 to 40 °C).
• Relative humidity must be < 90% non-condensing.
• Reinforce wall structure for panel weight and local
codes; see table.
• Allow 12 in (305 mm) clearance above and below
panel.
• Mount within 7° of true vertical.
• Mount panel where audible noise is acceptable.
(Internal relays click.)
• Mount panel so line (mains) voltage wiring is
at least 6 ft (1.8 m) from audio or electronic
equipment and associated wiring.
• Install in accordance with all national and local
electrical codes.
• This equipment is air-cooled. Vents must not be
blocked or you will void the warranty.
• 230 V
panels with 13 A circuit breakers are
intended for industrial or commercial use only.
Front View
Load circuit wiring
Air flow
Low-voltage
control
wiring for
1
TVM loads
2
3
4
Do not
obstruct
5
vents!
6
7
8
PELV
(Class 2: USA)
A
Wiring
B
C
N
Feed wiring
LP8/32-1204ML-20 shown
8
Installation Guide for Dimming and Switching Panels
Side View:
Side View:
Surface Mount
Recess Mount
Air flow
No.
Max. Heat
Modules
BTUs (Kcal)/Hr.
1
90 (22.68)
2
170 (42.84)
3
250 (63.00)
4
330 (83.16)
5
410 (103.32)
6
490 (123.48)
7
570 (143.64)
8
650 (163.80)
9
730 (183.96)
Surface Mounting
• Lutron recommends using 1/4 in (6 mm)
mounting bolts (maximum size accepted by
keyholes).
• Reinforce wall structure as required for weight
and local codes.
• Do not mount panel directly to wall board/
drywall.
Recess Mounting
• Mount to wall stud by screwing through slots in
corners of panel.
• Mount panel between flush and 1/8 in (3 mm)
below finished wall surface.
Recommended Mounting Heights*
(for LCP128
systems)
TM
Mini
45 in (1143 mm)
Standard
25 in (635 mm)
* Measure from floor to bottom of panel;
optimal viewing height for controller.
Max. Weight w/o
Packaging
Pounds (kg)
24 (11)
35 (16)
37 (17)
68 (25)
71 (26)
74 (27)
77 (28)
80 (29)
83 (30)
®