Feed-Through Panel: Feed and Load Wiring (all voltages)

General Notes

• Typical dimming/switching legs shown.
• Do not remove bypass jumpers until after load wiring has been
verified.
Wire sizes for power feed, to each input
• Power feed: 14 to 10 AWG (2.5 to 4.0 mm
• Neutral feed: 14 to 10 AWG (2.5 to 4.0 mm
Wire sizes for load wiring, from each output
• Dimmed hot (live): 14 to 10 AWG (2.5 to 4.0 mm
• Load neutral: 14 to 10 AWG (2.5 to 4.0 mm
Control Circuit Power
• Supplies power for internal operation.
• Requires dedicated feed with same voltage and phase as panel.
• Must be 1/4 in (6 mm) away from PELV (Class 2: USA) control wiring
harness.
• Panel voltage (see pages 2 to 3) indicates feed voltage.
• For 230 V
and 240 V
Therefore, terminals will be labeled L and DL.
4-Circuit Dimming Module (4U)
4-Circuit Adaptive Dimming Module (4A)
4-Circuit ELV Dimming Module (4E: 230 V
4-Circuit Quiet Fan Speed Module (4FSQ)
Dimmed hot/live
Circuit breaker
Load
Hot/Live
Feed
Neutral
Neutral
4-Circuit Switching (Relay) Module (XP)
Circuit breaker
Switched
Hot/live
hot/live
H1
SH1
H2
Load
SH2
Feed
H3
SH3
H4
SH4
N
Neutral
To distribution
panel
12
Installation Guide for Dimming and Switching Panels
2
)
)
2
)
2
panels, "Hot" is referred to as "Live".
and 220 to 240 V
Bypass jumper
DH
DH
DH
DH
H
N
N
N
N
N
Bypass jumper
)
2
only)
TVM Module
For 0-10 V, PWM, Tridonic
TVM controls two consecutive circuits of lighting and
are the first circuits in the panel. Maximum low-voltage
ballast control current: 50 mA per zone, 750 mA per panel.
Dimming or switching module is used to switch power to
the ballast.
Dimmed hot/live
N
H/L
Circuit breaker
Hot/Live
Feed
Neutral
Neutral
See terminal
block modules
for specific wiring
details.
DSI, and DALI loads. Each
®
+
Ballast
Bypass jumper
DH
DH
DH
DH
H
N
N
N
N
N
TVM
+ 1 –
+ 2 –
®

Publicité