Panel Model Number Guide
GRAFIK Systems
Example
C C P - 1 X 4 L 2 T - 2 3 0 4 I S - C E - L C P - C G P _ _ _
Prefix
Modules:
Quantity
and Type
Prefix
CCP = Custom combination panel
Module Types
_X _L _E _A _M _T
List modules in the order shown above. Insert the
quantity before each module code. Omit codes for
modules not used in panel. See table below for limits
on numbers of modules per panel.
X = Four-Circuit Switching (Relay) (XP)
L = Four-Circuit Dimming (4U)
E = Four-Circuit Electronic Low Voltage Dimming (4E)
A = Four-Circuit Adaptive Dimming (4A)
M = Four-Circuit Motor (4M)
T = 0-10 V, DALI (broadcast), DSI, and PWM
Ballast Control (TVM)
Feed Voltage
230 = 230 V
(CE)
240 = 220 to 240 V
(non-CE)
Feed Type
FT = feed-through panel (circuit breakers not included)
4IS = 3 phase 4 wire isolation switch
2M = 1 phase 2 wire input breakers (mini only)
4M = 3 phase 4 wire input breakers (mini only)
Module Quantity Limits
Panel Size
Feed type
Mini
Feed-through
Mini
Feed-through
Mini
Input breakers
Mini
Input breakers
Standard
Feed to through
Standard
Input breakers
Standard
Input breakers
Notes
• Consult Lutron for panels with custom breaker needs.
• TVM = 0 is a TVM-ready panel; TVM modules can easily be installed in the future.
• TVM = NA is not TVM-ready
®
(CCP/LCP) (230 / 220 to 240 V
TM
Feed
Region
Voltage
Suffix
Feed
Type
Feed Current
10 A to 125 A
10 A to 125 A
TVM
4A
NA
Any combination up to 3 modules
0 to 4
Any combination up to 2 modules; must have 1 4U or XP module
minimum; each 4U or XP module can control only 2 TVM modules
NA
Any combination up to 3 modules
0 to 4
Any combination up to 2 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules
0 to 12 Any combination up to 8 modules; must have 1 4U or XP module
minimum; each 4U or XP module can control only 2 TVM modules
0 to 12 Any combination up to 8 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules
0 to 12 Any combination up to 6 modules; must have 1 4U or XP module
minimum; each 4U or XP module can control only 2 TVM modules
(continued)
Custom
Panel Suffix
Controller
(contact Lutron for custom options)
Type
Region Suffix
CE = 230 V
AU = 220 to 240 V
Note: Should match feed voltage
Controller Type
Omit for single-link circuit selector
2L = 2Link
circuit selector
TM
LCP = LCP128
TM
Custom Panel Suffix (optional)
Indicates panel with special options
Frequency
(All Model Numbers and Voltages)
50 / 60 Hz
Output (Load) Ratings
Module Type Rating
XP
16 A per circuit
4U (230 V
) 13 A per module, 10 A per output
4U (240 V
) 16 A per module
4A
13 A per module, 8 A per output
4E
16 A per module, 10 A per output
4M
16 A per module, 5 A per output
(1/4 HP motor), 1 motor per output
TVM
50 mA per channel, 750 mA per system
4U
4E
Installation Guide for Dimming and Switching Panels
only)
4M
XP
0
0
0
5