Panel Model Number Guide

LCP128
(LCP) (120 V
TM
See page 5 for 230 / 220–240 V
Example
L C P - 2 X 2 D 1 A 4 T - 1 2 0 4 M L - 2 0
Prefix
Modules:
Quantity and Type
Prefix
LCP = LCP dimming panel
Module Types
_X _S _D _Q _A _M _F _T
List modules in the order shown above. Insert the
quantity before each module code. Omit codes for
modules not used in panel. See table below for limits
on numbers of modules per panel.
X = Four-Circuit Switching (Relay) (XP)
S = One-Circuit Dimming (1U)
D = Two-Circuit Dimming (2U)
Q = Four-Circuit Dimming (4U)
A = Four-Circuit Adaptive Dimming (4A)
M = Four-Circuit Motor (4M)
F = Four-Circuit Quiet Fan Speed (4FSQ)
T = 0-10 V, DALI (broadcast), DSI, and PWM
Ballast Control (TVM)
Feed Voltage
Feed Current
120 for 120 V
20 A or 175 A
Module Quantity Limits
Panel Size
Feed type
Mini
Feed-through
Mini
Feed-through
Mini
Breakers
Mini
Breakers
Standard
Feed-through
Standard
Feed-through
Standard
Breakers (main lugs)
Standard
Breakers (main lugs)
Standard
Breakers (main lugs)
Standard
Breakers (main lugs)
Notes
• Consult Lutron for panels with custom breaker needs.
• TVM = 0 is a TVM-ready panel; TVM modules can easily be installed in the future.
• TVM = NA is not TVM-ready
2
Installation Guide for Dimming and Switching Panels
only)
Feed
Branch Circuit
Voltage
Breaker Rating
Feed
Type
TVM
4A
NA
Any combination up to 3 modules
0 to 4
Any combination up to 2 modules; must have 1 4U or XP module
minimum; each 4U or XP module can control only 2 TVM modules
NA
Any combination up to 3 modules
0 to 4
Any combination up to 2 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules
NA
Any combination up to 9 modules
0 to 12 Any combination up to 8 modules; must have 1 4U or XP module
minimum; each 4U or XP module can control only 2 TVM modules
NA
Any combination up to 9 modules
NA
Any combination up to 7 modules
0 to 12 Any combination up to 7 modules;
must have 1 4U module minimum;
each 4U module can control only 2 TVM modules
0 to 12 Any combination up to 5 modules; must have 1 4U or XP module
minimum; each 4U or XP module can control only 2 TVM modules
Feed Type/Input Ratings
FT = Feed-through panel (circuit breakers not included)
/ 120 V
3M or 3ML = 1 phase 3 wire feed (split phase) /
120 / 240 V
4M or 4ML = 3 phase 4 wire feed / 120 / 208 V
Branch Circuit Breaker Rating
Omit for feed-through panels
20 for 20 A branch circuit breakers
Frequency - All Model Numbers and Voltages
50 / 60 Hz
Output (Load) Ratings
Module Type Rating
XP
16 A per circuit
1U, 2U, 4U
16 A per module
4A
16 A per module, 10 A per output
4M
16 A per module, 5 A per output
(1/4 HP motor),
1 motor per output
4FSQ
2 A per output (single ceiling fan)
TVM
50 mA per channel, 750 mA per system
4U
4M
XP
0
0
0
0
®