Vertical Termination - Napoleon BHD4N Série Instructions D'installation Et D'opération

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

18
3.10

VERTICAL TERMINATION

EN
Simple venting configurations.
For vent configurations requiring more than one 45° and one 90° elbow, the following formulas apply:
Formula 1: H
T
Formula 2: H
T
Example:
V
= 5 FT (1.5m)
1
V
= 10 FT (3.1m)
2
V
= V
+ V
= 5 FT (1.5m) + 10 FT (3.1m) = 15 FT (4.6m)
T
1
2
H
= 3 FT (0.9m)
1
H
= 2.5 FT (0.8m)
2
H
= H
+ H
= 3FT (0.9m) + 2.5FT (0.8m) = 5.5 FT (1.7m)
R
1
2
H
= .03 (one 45° + three 90° elbows - 135°)
O
= .03 (45 + 270 - 135°) = 5.4 FT (1.6m)
H
= H
+ H
= 5.5 FT (1.7m)+ 5.4 FT (1.m) = 10.9 FT (3.3m)
T
R
O
H
+ V
= 10.9 FT (3.3m)+ 15 FT (4.6m) = 25.9 FT (7.9m)
T
T
Formula 1:
Formula 2:
Since both formulas are met, this vent configuration is acceptable.
W415-1285 / F / 12.21.16
< V
T
+ V
< 40 feet (12.2m)
T
H
< V
T
T
10.9FT (3.3m) < 15 (4.6m)
H
+ V
< 40 FT (12.2m)
T
T
25.9FT (7.9m) < 40 (12.2m)
(H
) < (V
)
T
T
See graph to determine the required vertical rise V
required horizontal run H
40 (12.2)
30 (9.1)
REQUIRED
VERTICAL
20 (6.1)
RISE IN FEET
(METERS) V
T
10 (3.1)
3 (0.9)
0
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) H
The shaded area within the lines represents acceptable
.
T
5
10
15
(1.5)
(3.1)
(4.6)
values for H
and V
T
T
90°
H
2
V
1
45°
H
1
90°
18.3A
for the
T
20
(6.1)
T
V
2
90°

Publicité

Chapitres

Table des Matières
loading

Table des Matières