Models
UX09*E5*, UX12*E5*,
UD12*E5*, UD16*E5*
Terminals on the indoor unit
Colour of wires
Terminals on the outdoor unit
Models
UX09*E8*, UX12*E8*,
UX16*E8*, UD09*E8*,
UD12*E8*, UD16*E8*
Terminals on the indoor unit
Colour of wires
Terminals on the outdoor unit
CAUTION
•
For three phase model never operate the unit by pressing the
electromagnetic switch.
•
Never correct the phase by switching over any of the wires inside
the unit.
6
ACXF60-03260.indb 6
Flexible cable specifi cation
4 x min 4.0 mm
2
or 6.0 mm²
1
2
3
1
2
3
Earth Wire
must be
longer than
others cables
for safety
reason.
Flexible cable specifi cation
6 x min 1.5 mm
2
1
2
3
4
5
1
2
3
4
5
Earth Wire
must be
longer than
others cables
for safety
reason.
•
Select required direction and apply protective bushing
provided in accessories to protect cables from sharp edges.
•
Once all wiring work has been completed, tie the cable and
cord together with the binding strap so that they do not touch
other parts such as the compressor and bare copper pipes.
Outdoor Unit
Protective
bushing 3
Apply cut
DETAIL OF CONNECTING CABLE GUIDING
WIRE STRIPPING AND CONNECTING REQUIREMENT
Wire stripping
Indoor/outdoor
connecting terminal
board
5 mm or more
(gap between wires)
No loose strand when insert
Conductor over
Conductor fully
insert
insert
ACCEPT
PROHIBITED
6
PIPE INSULATION
1. Please carry out insulation at pipe connection portion as mentioned
in Indoor/Outdoor Unit Installation Diagram. Please wrap the
insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may
form), please increase the insulation by using POLY-E FOAM with
thickness 6 mm or above.
Indoor/outdoor unit
terminal board
Cord clamp
Banding strap
(Field Supply)
Connecting cable
(refer below
diagram for its
guiding)
Selection
of direction
Conductor not
fully insert
PROHIBITED