Specifications - Megger TDR1000/2 Guide De L'utilisateur

Masquer les pouces Voir aussi pour TDR1000/2:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 20

Specifications

Batteries:
Six LR6 (AA) type batteries,
Manganese-alkali or
nickel-cadmium or
nickel-metal-hydride cells
Nominal voltage:
9V for Alkali or 7.2V for NiCad.
Battery consumption:
100mA nominal, 140mA with backlight.
(20/30 hours continuous use depending
on backlight use)
Safety: This instrument complies with IEC61010-1
for connection to live systems up to 300V
CAT III ***Phase to ground (415 V phase to
phase). Fused leads must be used if the
voltage between the terminals exceeds
150V.
EMC:
Complies with Electromagnetic
Compatibility Specifications (Light,
industrial) BS EN 61326-1, with a
minimum performance of 'B' for all
immunity tests.
Mechanical
The instrument is designed for use indoors or
outdoors and is rated to IP54.
16
Case Dimensions: 230 mm long (9 inches)
115 mm wide (4.5 inches)
48 mm deep (2 inches)
Instrument weight: 0.6kg (1.32lbs)
Case material:
ABS
Connectors:
Two 4mm-safety terminals.
Test Lead:
2 metres long consisting of
2 x 4mm shrouded
connector to miniature
crocodile clips
Display:
128 64 pixel Graphics LCD.
Environmental:
Operational Temperature:
-15C to +50C (5F to122F)
Storage Temperature:
-20C to 70C (-4F to158F)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Tdr1000/2p

Table des Matières