power lines.
– Cables and their insulation should be in accordance
with the intended temperature, voltage and power
ranges. The standards of the respective countries
apply.
DC versions:
Use shielded wires for the counting and control inputs
so as to obtain the maximum EMC resistance or con-
nect not used count inputs to ground (0 V).
AC versions:
Use shielded wires for the counting and control inputs
so as to obtain the maximum EMC resistance.
1.9 Start-up
Is the device set and programmed correctly (function;
for counters, max. counting frequency)?
Overview
Model
Operating
mode
6.134.012.8x0
Timer
6.134.012.8x1
6.134.012.8x3
6.135.012.8x0
Timer
6.135.012.8x1
6.135.012.8x3
Table 1
DC operating modes:
Timer:
INP A:
no function
INP B:
Timer-Enable-Input

Main technical features:

Display:
LCD, 8 decades, height of the figures 8 mm
Display range:
0 ... 99999999 with leading zeros
suppression.
Accuracy: < 100 ppm
Note:
For one ON/OFF-cycle the counter can lose
max. one impulse of the selected time range
Overflow: In case of a display range overflow, the timer
starts again from 0, but without removing the
leading zeros and activating all decimal
points.
Keys:
Electrical locking of the reset key
6
Time range
Inputs
INP A
99999h 59 m/
––
99999.99 h
10 ... 260 V AC/DC
9999 h 59 m 59 s/
––
9999999.9 s
10 ... 260 V AC/DC
1.10 Failure possibilities and causes
Impossible to use the keys:
- Key lock input activated
Counter does not count:
- Wrong or reversed wiring of the counting input
- Setting of an input signal not matching the pulse gen-
erator
- Polarity (NPN/PNP) reversed
- No ground connection between the pulse generator
and the counter
- Signal levels do not reach the switching threshold of
the counter
If, despite all, your device still does not operate, contact
your local representative or call us directly for technical
support.
When sending your device back, please attach a short
description of the failure, of the programming and of the
connection diagram, in order to allow us to reproduce a
possibly existing defect and to repair your device as
quickly as possible.
AC/DC
AC/DC
Options:
x = 5: no backlight
x = 6: with backlight
AC operating modes:
Timer:
INP A:
Timer-Enable-Input AC/DC
INP B:
reset input AC/DC
Housing: Panel mounting, 48 x 24 mm
according to DIN 43 700, RAL 7021
Panel cut-out:
22,2
+0,3
x 45
Mounting depth:
approximately 48 mm
Weight:
approximately 50 g
Protection level:
IP65 on the front side
INP B
00 ... 0,7 V DC
04 ... 30 V DC
10 ... 260 V AC/DC
00 ... 0,7 V DC
04 ... 30 V DC
10 ... 260 V AC/DC
+0,6
mm
NPN
PNP
AC/DC
NPN
PNP
AC/DC