Approvals
Approvals (valid for marked equipment)
Construction Product
PA 1: VdS 0786-CPD-21182
Regulation
(305/2011/EC )
12
VdS
PA1: G 212115, PA X 1-05: G 212188 /
GL
61062-13 HH
MED
MEDB00002BH
CNBOP
PA 1: 2015/2014
PA 1
UL, cUL
PA 1
PA X 1-05
PA X 1-05
PATROL sounders and combined units PA 1/ PA X 1-05 comply with the limits for a Class B digital device, pursuant to
part 15 of the FCC Rules.
UL/ cUL specifications:
Suitable for indoor and outdoor use. Signaling area: see document 30303-005-1.
Cable gland entries:
Conduit installation needs to be UL/ cUL listed fittings suitable for knockout openings. The supply wiring has to be enclosed in metal
conduits for products for Fire Alarm Use.
According to CSA-C22.2 No. 205-M1983 clause 4.3.4 the connection is limited to max. three leads.
Installation:
The units shall be installed indoors or outdoors in accordance with the manufacturer's installation instructions as well as the National
Electrical Code (NFPA 70) and the National Fire Alarm Code (NFPA 72) for the units evaluated for Public Fire Alarm applications in the
U.S. In Canada, they shall be installed in accordance with the Canadian Electrical Code, Part 1 and the Standard for the Installation of
Fire Alarm Systems CAN/ULC-S524-M91 for the units evaluated for Public Fire Alarm applications. The installation shall also be in a
manner acceptable with the local authority having jurisdiction.
For audible application for Fire Alarm Service use both terminals for connection. Break wire run to provide Electrical Supervision (see
UL 464 clause 39.1e). The tone no. 111 is to be used for evacuation use only
(see UL 464 clause 39.1e)
cUL directional characteristics for
the horn:
Min. Output sound pressure
level: [dB(A)]
Connecting cables:
085 501 944t
Options
Rated voltage
Operating voltage range
acc. to EN54-3, EN54-23
Lens colours of beacon
Tone
2
15
60
104
131
146
Signaling area
Environmental
protection class
Installation position
Testing takes place using the supplied diaphragm nipple and the outer fastening bores.
Environmental Category C, H, EMC1
Rated
Voltage
24V – 48V DC
(Fire Alarm Equipment)
12V – 48V DC
(General Signal Equipment)
24V AC
115V AC
230V AC
12V DC
24V DC
48V DC
AXIS
Horizontal
Horizontal
Vertical
Vertical
Type
Voltage
PA 1-24 DC
18V DC
Tone no. 2, 15, 60, 104, 131, 146, 111, 112, and 113 was used for this test.
PA X 1-05: 0786-CPD-21220
PA 1
–SSM (24V DC)
24 – 48V DC
18V – 57V
Option: -SSM (18V – 30V)
-
Compliant with the Construction Product Directive (89/106/EWG)
1200Hz-500Hz (Saw tooth) DIN/PFEER P.T.A.P.
500Hz-1200Hz (Slow whoop)
825Hz (Continuous)
660Hz (Intermittent tone)
800Hz/ 1000Hz (Alternating tone)
544Hz/ 440Hz (NF S 32-001)
EN54-3:
see document 30303-005-1
arbitrary
Data see Construction Product Regulation (305/2011/EC)
Audible-signal Appliance
Fire Alarm Equipment
ULSZ, ULSZ7
x
Special application, limited operat-
ing voltage range 18 – 57V DC
-
-
ANGLE
32 deg. left or right
28 deg. left or right
32 deg. left or right
28 deg. left or right
UL 464 dB(A) at 10 ft ++
77,1 (for tone 113)
30303-004t
PA X 1-05
24V DC
48V DC
18 - 30V
40 - 57V
red, clear
EN 54-23 Category O:
see document 30303-005-1
Type B
Light faces down
PA X 1-05: 2017/2014
Audible and Visual signal Appliance
General Signal Equipment
UCST, UCST7 and UEES, UEES7
x
x
x
dBA
-3
-6
-3
-6
CAN/ULc-S525-07
86,2 (for tone 60)
7