5.3

MINIMUM ENCLOSURE CLEARANCES

TOP VENT
432mm
53 "
1346mm
CEILING
4 1/2"
114mm
(MIN)
TOP EXIT ENCLOSURE
The appliance requires a minimum enclosure height of 53" (1346mm). For temperature requirements, the
enclosure space around and above the appliance must be left unobstructed.
NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of the combustible
wall penetration.
* See "MINIMUM FRAMING DIMENSION" section for details on reducing vent pipe top clearances.
These parameters also apply to the illustrations found in the "MINIMUM ENCLOSURE CLEARANCES" section.
5" 127mm
17"
STEEL HEADER
TOP OF FIREPLACE
OPENING
31 1/2"
800mm
NON-COMBUSTIBLE
COMBUSTIBLE
7" 178mm
MIN
NON-COMBUSTIBLE
MATERIAL
1" 25mm
3" 76mm
0" (0mm) IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK AND
STONE.
1" 25mm
41 1/8"
1045mm
MIN PLUS
RISE*
W415-1442 / C / 06.06.16
33
EN