4.4
minimum enclosure clearances (GSS48E - one sided)
WARNING
!
•
Use only non-combustible materials (certified to ASTM E-136) such as steel studs, cement board, ceramic tile,
marble, paint, etc. When adding finishing materials to the appliance, do not use wood or drywall.
•
You must have clear and easy access to the on/off valve AFTER the appliance is installed and connected to the
gas supply in order to safely turn off the burner.
36"
(914mm)
minimum
to ceiling.
60 3/4"
(1543mm)
minimum to
ceiling.
24 3/4" (629mm)
Including 1/8"
(3mm) clear-
ance per side.
6"
(152mm)
6"
(152mm)
minimum
to floor
note:
Ensure complete enclosure is closed
to prevent rain and debris from falling
on top of the appliance, as well as to
ensure no draft will occur through the
enclosure.
NON COMBUSTIBLE
6"
(152mm)
50 3/4" (1289mm)
(Including 1/8"
(3mm) clearance
per side)
36"
(914mm)
minimum
to ceiling.
6"
(152mm)
minimum
to floor
1 1/2"
(38mm)
6"
(152mm)
Gas and electrical lines protrude
from the bottom of the appliance
located on the right side.
All material in
shaded area must
be Non Combustible
(including framing,
sheeting and
finishing materials).
Certified to ASTM
E-136
1/2"(13mm) Cement
Board
6"(152mm)
Steel Stud
6" (152mm)
(Minimum
clearance to
combustibles)
framing
EN
All material in
shaded area
must be Non
Combustible.
(including framing,
sheeting and
finishing materials).
Certified to ASTM
E-136
Nailing Tabs (4 per
side)
15
W415-3006 / A / 05.27.21