8.1.4
With Heat Shield AC02710 and Lowered Ceiling
To reduce the clearances of an appliance using a single wall pipe connector, the use of a heat
shield certified with the single wall pipe connector to be used as close as 6" from combustible
materials must be used. Only in this case, the same clearances as a certified double wall pipe
connector can be used.
APPLIANCE CLEARANCES
WITH DOUBLE WALL PIPE
CONNECTOR
Canada
A
2 ½" (64 mm)
B
2 ½" (64 mm)
C
2 ½" (64 mm)
78" (1981 mm)
L
8.1.5
Inside an Alcove
APPLIANCE CLEARANCES
WITH DOUBLE WALL PIPE
CONNECTOR
Canada
A
11" (279 mm)
12" (305 mm)
B
K
48" (1219 mm)
78" (1981 mm)
L
8.1.6
Mobile Home
It is strictly forbidden to install a unit with a single wall pipe in a mobile home.
APPLIANCE CLEARANCES
WITH DOUBLE WALL PIPE
CONNECTOR
Canada
A
12" (305 mm)
B
14 ½" (368 mm)
C
12" (305 mm)
The pipe distances listed in this table refer to the distances obtained when the stove is installed in accordance with the appliance clearances above
3
mentioned.
USA
2 ½" (64 mm)
2 ½" (64 mm)
2 ½" (64 mm)
78" (1981 mm)
USA
11" (279 mm)
12" (305 mm)
36" (914 mm)
78" (1981 mm)
USA
12" (305 mm)
14 ½" (368 mm)
12" (305 mm)
DISTANCES
CONNECTOR WITH DOUBLE
WALL PIPE CONNECTOR
Canada
D
6" (152 mm)
E
11 ½" (292 mm)
F
11 ¼" (286 mm)
DISTANCES
CONNECTOR WITH DOUBLE
WALL PIPE CONNECTOR
Canada
D
14 ½" (368 mm)
E
21" (533 mm)
DISTANCES
CONNECTOR WITH DOUBLE
WALL PIPE CONNECTOR
Canada
D
15 ½" (394 mm)
E
23 ½" (597 mm)
F
20 ¾" (527 mm)
FROM PIPE
3
USA
6" (152 mm)
11 ½" (292 mm)
11 ¼" (286 mm)
FROM PIPE
3
USA
14 ½" (368 mm)
21" (533 mm)
FROM PIPE
3
USA
15 ½" (394 mm)
23 ½" (597 mm)
20 ¾" (527 mm)
Page 35