3.3

Technical data

Model
Max. power supply pressure
Protection level
Ambient temperature
Electromagnetic valve
Voltage/frequency
Output/absorption
Anti-dust device
3.4
Components
The Multibloc is composed by:
Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Gas pressure switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
3.5
Description
8
6
1
Input pressure test point
2
Output pressure test point
3
Brake adjustment (slow ignition)
4
Valve adjustment (main delivery)
5
Pressure adjuster calibration
6
Minimum gas pressure switch
7
Gas-in flange
8
Flange fixing screws
9
Gas-out flange
10 Coil
11 6-pin plug unit
12 Pressure switch connector
13 Valve connector
2902647
Technical description
IP 54 IEC 529 (EN 60529) with adequate protection of the 6 pole socket/plug
3
2
13
5
10
8
4
1
12
7
MBC 65/1
65 mbar (6,5 kPa)
-15°C up to + 60 °C
DIN EN 161, class A, group 2
~ (AC) 50-60 Hz, 220-230 V -15 % +10 %
18 VA a ~(AC) 230 V, 20 °C
Small filter with 120 µm mesh
Pressure stabiliser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Rapid opening safety valve . . . . . . . . . . . . . . . . . . . . . . . . No. 1
Slow opening adjustment valve . . . . . . . . . . . . . . . . . . . . . No. 1
6
8
4
GB
11
S8714
9
Tab. B
Fig. 1