Pressure Loss - Riello MBC 65/1 - RSD 20 Manuel D'entretien

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 23
5.5

Pressure loss

The gas train pressure loss p is provided from the diagram (Fig.
8); the scales of the volumetric output
for:
a
air,
n
natural gas (G20),
p
propane (G30),
c
town gas (G140), only for applications not covered by the
Gas Appliances Directive (2009/142/EC).
20060492
Activation, calibration and functioning
V °
are valid respectively
9
GB
The values, provided from the diagram, can be different accord-
ing to the pressure regulator calibration.
The minimum necessary pressure in the network can be obtained
by adding the pressure of the diagram to the burner pressure
losses (see burner manual) and the back pressure of the com-
bustion chamber (see heat generator manual).
Fig. 8
2902647

Publicité

Table des Matières
loading

Table des Matières