10.6. How to install branch pipe
For detail, please observe the instruction manual attached to the op-
tional refrigerant branch kit.
Joint
A
A To outdoor unit
B To branch piping or indoor unit
•
Apart from the CMY-Y202-F and CMY-Y302-F gas side, there are no
restrictions on the posture for attaching joints.
•
Ensure that the branch pipes for the CMY-Y202-F and CMY-Y302-F
gas side are attached horizontally or facing upwards (see the dia-
gram below).
Horizontal
Within ± 15°
•
There is no limitation on the joint mounting configuration.
•
If the diameter of the refrigerant piping selected by the procedures
described on pages 14 to 15 is different from the size of the joint,
match the sizes using a deformed joint. The deformed joint is in-
cluded with the kit.
Header
A
A To outdoor unit
B To indoor unit
•
No restriction is applied to the mounting posture of the header.
•
If the diameter of the refrigerant piping selected using the proce-
dures described on pages 15 and the size of the joint is different,
match the sizes using a deformed joint. The deformed joint is in-
cluded with the kit.
B
Facing upwards
(Facing downwards is not possible)
Within ± 15°
Within ± 15°
B
C
C Pipe cutter
D or
E Deformed joint
•
When the number of pipes to be connected is smaller than the number
of header branches, install a cap to the unconnected branches. The
cap is included with the kit.
Distributer (liquid)
Field piping
Field piping
Variable
Variable
capacity unit
capacity unit
•
Mount the distributor (liquid, optional CMC-30A) so that it is within
±15° in relation to the horizontal plane (see figure above).
D
E
±15°
Constant
Constant
capacity unit
capacity unit