IFM efector800 VSE001 Manuel D'utilisation page 17

Electronique de diagnostic pour capteurs de vibration
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

13...16
connections to the sensor 2 (type VSAxxx)
17...20
connections to the sensor 3 (type VSAxxx)
21...24
connections to the sensor 4 (type VSAxxx)
Protect the supply voltage externally (max. 2 A)!
The terminals of the DC supply are directly connected to the terminals
of the sensor supply. The SELV criteria must therefore be met for the
DC supply (safe extra-low voltage, circuit electrically separated from
other circuits, not grounded).
If the DC circuit is to be grounded (e.g. due to national regulations),
the PELV criteria must be adhered to (safe extra-low voltage, circuit
electrically separated from other circuits).
Connection of the sensors
Adhere to the SELV criteria when connecting the sensors so that no
dangerous contact voltages are applied or transferred to the sensor!
The sensor and VSE supply are not electrically separated.
Monitoring of the sensor cable: In case of wire break or short circuit
the output [OUT 2] switches and the LED [SENS] of the sensor flash-
es green.
Ethernet connection
The RJ45 socket is used for connection to the Ethernet configurable to
10 or 100 Mbits/s (= 10 / 100 Mbd).
Ethernet cables are available as accessories, e.g.:
Cross-over cable 2 m
Cross-over cable 5 m
article no. EC2080
article no. E30112
17

Publicité

Table des Matières
loading

Table des Matières