10
Connection for display, GSM or ISDN unit module, RJ 12/RS 232, 24 V
11
Ethernet interface, RJ 45 with PoE
12
CAN bus connection (daisy chain) for CMC III sensors and control units, 24 V
13
Second CAN bus connection (not for the "Compact" variant), 24 V
14
24 V
power supply (power pack connection)
15
24 V
power supply (direct connection)
16
Alarm relay output (floating contact, max. 24 V
Note:
The voltage sources at positions 7, 10, 12, 13 and 16 (fig. 3) must satisfy the Limited
Power Source (LPS) requirements in accordance with UL 60950 and observe the limit val-
ues mentioned above.
The F5 fuse with the following specification – 450 V
Littlefuse – is also installed in CMC III PU.
5.2
Installation
Note:
The unit is free from power only after all power sources have been disconnected!
Insert the external temperature sensor at the rear on the CMC III PU connection (fig. 1, item 9) and
route the measuring sensor to the required measuring point.
Note:
The internal temperature sensor will be disabled when the external temperature sensor is
inserted.
Note:
The external temperature sensor must be connected before the CMC III PU is started.
If the external temperature sensor is connected during running operations, the CMC III PU
must be restarted so that the external temperature sensor is detected and used.
Connect the external power pack (DK 7030.060) to the 24 V power supply connection (fig. 3,
item 14).
The device start takes approx. 1 minute. During this time, the status display flashes blue in irregular
intervals (fig. 3, item 3).
The device is operational when the status display lights green continually.
If, after completion of the switch-on process, the status display flashes red-blue, keep the "C" key
pressed to acknowledge pending messages (fig. 3, item 1).
The status display then lights green continually and the device is operational.
If the installation is not successful: see section 1.1.
Rittal CMC III Processing Unit / CMC III Processing Unit Compact
Installation and operation
,1 A
, 1 A)
, 3.15 A, slow fuse, type 09773.15MXP
, 500 mA
,1 A
11
EN