8
Diagnostics

LED status displays

LED
Pos.
Colour
0
Yellow
1
Green
EDK82ZAFPC−201 DE/EN/FR 7.0
Condition
Description
Off
No communication with the PROFIBUS master.
Blinking
Communication with the PROFIBUS master has been established
via the function module.
Off
l
The function module is not supplied with voltage.
l
The standard device and/or the external voltage supply is/are
switched off.
Blinking
The function module is supplied with voltage but has not
established a connection to the standard device.
(const.)
Causes:
l
The standard device is switched off.
l
The standard device is in the initialisation phase.
l
The standard device is not available.
Blinking
Internal error of the function module
(3x short)
On
The function module is supplied with voltage and has established
a connection to the standard device.