13.3) Safety devices WITHOUT SELF-DIAGNOSIS but with voltage-free
Ex-CHANGE CONTACTS.
We conventionally make reference to a receiving device (RCS- fig.5) with 5
terminals which have the following functions: terminals 1 and 2 are for 24Vac
power supply, terminal 3 is a common terminal, terminal 4 is a normally closed
contact not in use, terminal 5 is a normally open contact not in use.
A) Fig. 19 "A" shows the wiring diagram for connecting the power supply to
those receivers and transmitters for which a self-diagnosis is required.
B) Fig. 19 "B". Connection of one or more receivers (photocell) of the same
type up to a maximum of four (Dip 9 OFF/Dip 10 ON, photocells only, leave
jumped 35-26). For example, if there are two photocells, connect F1 and
F2, then interrupt the connection chain by connecting the terminal 4 of
F2 to LOOP1 and the terminal 5 of F2 to COM. If only one receiver has
to be connected, connection must be made as shown in fig.19 ref.1. If the
receivers to be connected are less than four, it is necessary to interrupt
the connection chain by performing the connections as shown in fig.19
ref. 2 or 3. If rubber edges instead of photocells have to be connected,
use terminal 35-BAR of the control unit.
If the devices concerned are rubber edges instead of photocells, use terminal
35-BAR in the control unit (Dip 9 ON/Dip 10 OFF, leave jumped 29-26).
C) Connection of one photocell and one rubber edge.(Dip 9 OFF/Dip 10
OFF)
D) Connection of two photocells and one rubber edge.(Dip 9 OFF/Dip 10
OFF)
When connecting two rubber edges and one photocell, F1 and F2 in fig.19
"D" become 2 rubber edges, and C1 one photocell; invert the connections
PHOT and BAR of the control unit with one another.(Dip 9 OFF/Dip 10
OFF)
E) Connection of three photocells and one rubber edge. When connecting
three rubber edges and one photocell, F1, F2 and F3 (fig.19 "E") become
3 rubber edges and C1 one photocell; invert the connections PHOT and
BAR of the control unit with one another.(Dip 9 OFF/Dip 10 OFF)
F) Connection of three photocells and two rubber edges When connecting
three rubber edges and two photocells, F1, F2 and F3 (fig.19 "F") become
three rubber edges, C1 and C2 two photocells; invert the connections
PHOT and BAR of the control unit with one another.(Dip 9 OFF/Dip 10
OFF)
G) Connection of four photocells and one rubber edge. When connecting four
rubber edges and one photocell, F1, F2 , F3 and F4 (fig.19 "G") become
four rubber edges and C1 one photocell; invert the connections PHOT
and BAR of the control unit with one another.(Dip 9 OFF/Dip 10 OFF)
14) OPERATION LOGIC
14.1) Dip-switch
Dip 1 and 2 ......................................................................Photocells (FCH)
ON - Excludes photocell operation during gate opening, and immediately rever-
ses movement during the closing phase when the photocell is obscured.
OFF - In the case where the photocell is obscured by an obstacle during the
closing manoeuvre, the gate is stopped; when the obstacle is removed, the
gate reopens. In the case where the photocell is obscured by an obstacle
during the opening manoeuvre, the gate is stopped; when the obstacle is
removed, the gate continues to open.
Dip 3 ....................................................................... Impulse blocking (IBL)
ON - The Start / Start pedestrian impulse has no effect during the opening
phase.
OFF - The Start / Start pedestrian impulse during the opening phase causes
the gate to stop.
Dip 4 ................................................................... Automatic closing (TCA)
ON - Automatically closes the gate after a dwell time set by the TCA trimmer.
The automatic closing manoeuvre is activated after the gate has reached the
opening end-of-stroke position, after the gate opening time has ended, or
after the gate has stopped in the opening phase due to a Start impulse.
OFF - Excludes automatic closing.
Dip 5 2 or 4 step logic (2P/4P)
ON - A Start impulse given during the closing phase reverses the direction of
movement, during the opening phase it stops the gate. (Dip-switch OFF).
OFF - A Start impulse given while the gate is moving, causes it to stop; the
following impulse reverses the running direction. (4-step logic).
N.B.: The Start impulse in the opening phase has no effect when Dip-switch
3 is ON.
Dip 6 .......................................................................... Pre-alarm (PREALL)
ON - The blinker comes on about 3 seconds before the motor starts.
OFF - The blinker comes on at the same time as the motor starts.
Dip 7 .............................................................Open/Close command (U.P.)
Activates the signals connected to terminals 33-34.
ON - Hold-to-run operation: the manoeuvre continues as long as pressure
is maintained on the command button.
OFF - Separate automatic Open/Close operation: by means of an impulse,
it opens the gate if closed and vice versa.
INSTALLATION MANUAL
Dip 8 ............................. Reduced or normal operation time range (S.TW)
ON - TW operation time ranging between 1-90 seconds (TW.PED pedes-trian
operation time from 1 to 20 seconds).
OFF - TW operation time ranging between 3÷210 seconds (TW.PED pede-
strian operation time from 5 to 60 seconds).
Dip 9 ............................................................. Unchecked photocells (FNv)
Activates the photocell control logic.
ON - The photocells are excluded from the safety check cycle which is
carried out before each manoeuvre; however their logic state is analysed
(for connection, refer to the typical method of connecting photocells with
continuously active beams). This is used to connect photocells which have
not been checked or have internal self-diagnosing systems, and always
provide a voltage-free output contact.
OFF - The photocells are included in the Ok safety check cycle which is
carried out before each manoeuvre. For connection, refer to the enclosed
diagrams.
Dip 10 ................................................................... Unchecked edge (BAR)
Activates the rubber edge device control logic.
ON - The edge devices are excluded from the safety check cycle which is
carried out before each manoeuvre; however their logic state is analysed
(for connection, refer to the typical method of connecting infrared edges with
continuously active beams). This is used to connect IR edges which have not
been checked or have internal self-diagnosing system, and always provide
a voltage-free output contact.
OFF - The IR edge devices are included in the Ok safety check cycle which
is carried out before each manoeuvre. For connection, refer to the enclosed
diagrams.
14.2) Trimmer-set functions
TW.PED Sets the partial operation time of a sliding gate which is being used
for both vehicles and pedestrians.
TW
Sets the operation time during both the opening and closing phases
(adjustable from 3 to 210 seconds).
TCA
Sets the dwell time, after which the gate closes automatically (from
1 to 120 seconds).
14.3) LED functions
The SIRIOTEL control unit is provided with leds which are useful in identifying
any anomalies in the system.
(DL1)
Stays on when supplied with mains power and with F1 fuse in-
tact.
(DL2)
Comes on when the motor is activated during closing.
(DL3)
Comes on when the motor is activated during opening.
(DL4)
Comes on following the Start command or the activation of the first
radio-receiver channel.
(DL5)
Goes off when the block command is activated.
(DL6)
Goes off when photocells are not aligned, i.e. when obstacles are
present. When Dip-switch 9 is OFF, the photocells and related leds
are only activated during manoeuvring.
(DL7)
Goes off when the gate is in the completely open position, if pro-
vided with end-of-stroke device.
(DL8)
Goes off when the gate is in the completely closed position, if
provided with end-of-stroke device.
(DL9)
Comes on at the Start command for pedestrian gate.
(DL10)
Comes on with manual opening command.
(DL11)
Comes on with manual closing command.
(DL12)
Goes off when the pneumatic edge is activated. When Dip-
switch 10 is OFF, the edge and its related LED are only activated
during manoeuvring.
(DL13)
Comes on when the safety ring is closed.
(DL14)
Comes on when the safety micro has stepped in.
15) EMERGENCY MANOEUvRE
When the electric supply is disconnected or the automation is faulty, the leaf
must be opened manually.
15.1) Activation
•
Open the front actuator door using the key provided (fig.23).
At the time of opening, a safety microswitch stops the actuator (fig.23
- ref. "S") from operating electrically.
•
Take out the release key (fig.23 ref. "C") located inside the box and insert
it in the release screw (fig.24 ref. "V") .
•
Turn key "C" anticlockwise until the pinion drive system becomes com-
pletely loose.
This way, the pinion is released and the gate can be operated manu-
ally.
WARNING - Considering the leaf weight, it is recommended to guide the
leaf manually along the entire run, and absolutely avoid pushing it in an
uncontrolled way.
ENGLISH
SP4000 - SP4000 FAST - Ver. 05 -
17