HAZARDS DURING REFUELING AND EMERGENCY PROCEDURES
DANGER! In case of strong smell of flue gas!
Flue gases can cause fatal poisoning!
1. For safety keep all boiler doors and ash-pit doors tightly closed!
2. Air the room where boiler is installed!
3. Close the door oft he boiler room and doors to living areas!
DANGER! In the event of loss of electrical power!
- Do not open any Boiler or Ash-pit Door!!
- Do not load fuel into the boiler!
- Boiler Control automatically restarts after power fail restart
- One hour after power has returned, check system for normal operation and compare manometer reading to
initial settings. If system pressure is below, replenish water to the hydronic system according plumber's
instructions.
DANGER! In the event of runaway fire!
- Turn off Emergency Switch, if installed.
- Do not open any Boiler or Ash-pit Door!
- DO NOT SWITCH OFF MAIN ISOLATOR AT CONTROL SYSTEM!
- In case no Emergency Switch is installed:
1. Open Insulation Door slightly and keep it opened
2. Push Arrow-Down Key at Boiler Control to switch off ID-Fan
3. Keep Insulation Door opened
4. Do not open Ash-pit Door or any Boiler Door behind Insulation Door
- When there is no more risk of runaway fire, turn on Emergency Switch and close Insulation Door and resume
to normal operation of the system.
To cool overheated boiler (over 220°F / 105°C)!
- Do not open any Boiler or Ash-pit Door!
- Turn all thermostats in your house to their highest temperature settings and open all windows.
- Open all hot water faucets.
- When boiler temperature has dropped below 180°F (82°C), reverse the above steps.
- In case Safety Temperature Limit Switch automatically has been activated please refer to Owner's Manual.