I∆N nominal fault current (F4):
Press the function key F4 to select the nominal fault current:
Available nominal fault currents (sinusoidal testing current)
½ I∆N
1 I∆N
5 I∆N
-
Connect the measuring leads to the BENNING IT 105 as shown in figures 4 or 5 and apply them to the
test object.
-
Press the TEST key 4 to start the measurement.
-
The measured tripping time is shown on the main display K.
8.6.3 Tripping current RCD
-
Select the desired function RCD
-
The symbols of the function keys F1 A to F4 D are briefly shown on the digital display 2 . You can
use the function keys F1 to F4 3 to make the following settings:
F1
0° / 180°
0°/ 180° (F1):
0°:
Testing current with positive initial polarity
180°:
Testing current with negative initial polarity
RCD type (F2):
sinusoidal test current
pulsating test current
selective (delayed) RCD
For testing selective RCDs, measurement starts after a time delay of 30 seconds.
I∆N nominal fault current (F4):
Press the function key F4 to select the nominal fault current:
Nominal fault currents at RCD type AC
-
Connect the measuring leads to the BENNING IT 105 as shown in figures 4 or 5 and apply them to the
test object.
-
Press the TEST key 4 to start the measurement.
-
The measured tripping time is shown on the main display K.
03/ 2020
10 mA
30 mA
I
M with the rotary switch 1 .
I
F2
:
10 mA
30 mA
BENNING IT 105 CH
:
100 mA
F3
100 mA
300mA
300 mA
500 mA
500 mA
F4
I∆N
26