Measuring With The Benning It 105; Preparations For Measuring; Switching The Benning It 105 On/Off - Benning IT 105 CH Notice D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7.4 Loop impedance (Z
Measuring range
high test current:
0.20 Ω - 1999 Ω
without RCD tripping:
1.00 Ω - 1.99 Ω
2.0 Ω - 19.9 Ω
20 Ω - 1999 Ω
Mains voltage:
Nominal test current:
Fault current range (PFC):
7.5 Line impedance (Z
Measuring range
0.20 Ω - 1999 Ω
Mains voltage:
Nominal test current:
Short-circuit current range (PSC): 0 A - 26 kA, for measured values < 10 A and > 999 A, a "-" is noted as
7.6 RCD test
Measuring range
0 ms - 2000 ms (½ I∆N)
0 ms - 400 ms (I∆N, standard)
0 ms - 500 ms (I∆N, selective)
0 ms - 40 ms (5 I∆N)
Mains voltage:
Nominal test current:
Test current accuracy:
Tripping current range:
Tripping current accuracy: 10 %
Type AC:
Type A:

8. Measuring with the BENNING IT 105

8.1 Preparations for measuring

Operate and store the BENNING IT 105 only at the specified storage and operating temperatures. Avoid
continuous insulation.
-
Check the nominal voltages and nominal current on the safety measuring leads.
-
Strong sources of interference in the vicinity of the BENNING IT 105 might lead to unstable readings
and measuring errors.
Before starting the installation tester, always check it as well as all measuring leads and
wires for signs of damage.
8.1.1

Switching the BENNING IT 105 ON/OFF

-
Turn the rotary switch 1 from position "OFF" F to the desired measuring function to switch on the
BENNING IT 105.
03/ 2020
)
S
195 V - 253 V, 45 Hz - 65 Hz
< 15 mA (without RCD tripping)
3 A (high test current)
0 A - 26 kA, for measured values < 10 A and > 999 A, a "-" is noted as
decimal separator
)
I
195 - 253 V, 45 Hz - 65 Hz
328 V - 440 V, 45 Hz - 65 Hz
3 A
decimal separator
195 V - 253 V, 45 Hz - 65 Hz
10 mA, 30 mA, 100 mA, 300 mA (type AC, A) 500 mA (type AC)
- 0 %, + 10 % with I∆N and 5 I∆N
- 10 %, + 0 % with ½ I∆N
½ I∆N - 1,1 I∆N (type AC, sinusoidal)
½ I∆N - 1,5 I∆N (type A, pulsating)
testing current sinusoidal
testing current pulsating
BENNING IT 105 CH
Resolution
max. 0.01 Ω
0.01 Ω
0.1 Ω
1 Ω
Resolution
max. 0.01 Ω
Resolution
1 ms
1 ms
1 ms
1 ms
Accuracy
± (5 % + 5 digits)
± (5 % + 12 digits)
± (5 % + 12 digits)
± (5 % + 5 digits)
Accuracy
± (5 % + 5 digits)
Accuracy
± (5 % + 2 digits)
± (5 % + 2 digits)
± (5 % + 2 digits)
± (5 % + 2 digits)
20

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

044105

Table des Matières