Control; Control Panel; Operation - Parker 250 Manuel D'utilisation

Masquer les pouces Voir aussi pour 250:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5

Control

5.1

Control panel

Display
[
&
z
y
3
4
é
x
2
Reference
Name
I ON = dryer powered;
1
MAIN SWITCH
O OFF = dryer not powered
Yellow = dryer powered
2
POWER LED
Green = dryer operating
Off = no signal
3
WARNING LED
Flashing = Alarm or warning
4
DRAIN LED
Lit = Drain open
English
Keyboard mode
x
ON/OFF BUTTON
z
RESET BUTTON
é
1
HISTORY BUTTON
y
DRAIN BUTTON
*returns to STANDARD mode aft er 5 minutes.
5.2

Operation

Description
Operation status
With the MAIN SWITCH
working conditions are possible:
DRYER
STATUS
1
OFF
2
ON
3
REMOTE OFF
To switch from OFF to ON turned to "I ON" (and vice versa) press
!
In OFF status the unit remains powered until the MAIN SWITCH
&
turned to "I OFF".
Y
To manage REMOTE OFF mode, remove the bridge be-
tween terminals X4.0 and X4.10 (see par. 8.8.) and connect
the remote start/stop switch(to be provided by the customer).
In ON status, use the button with the following logic:
DRYER STATUS
STANDARD
MENU*
Switching no/off
Confi rm
Reset alarm/warnigng
Up
Alarm/warning log
Down
Condensate drain
Out
&
turned to "I ON" (dryer powered) three
[
DISPLAY
POWER LED (2)
OFF
Yellow
Dew point
Green
r.OF
Yellow
x
X4.0
X4.10
X4.0
X4.10
ON
REMOTE OFF
!
Do not activate ON status (refrigeration compressor operating)
more than 10 times in one hour.
Scheduled maintenance
[
Y
When the DISPLAY
alternatively shows the Sr warning
code and dew point, contact authorized assistance personnel for carry-
ing out scheduled maintenance indicated in par. 6.3 and for resetting the
warning code (see par. 5.4 in List of alarm/warnings).
z
Press
to cancel the warning for 24 hours.
Condensate drain
Th ere are two operation modes:
• TIMED - check that the automatic condensate drainage system is
working properly.
Use manual drainage to check that condensate is not retained as this
is symptomatic of poor drainage.
Th is check of the timed drain opening (parameter d1).
Settings depends upon the operating conditions of the dryer and var-
ies the amount of condensate to be removed.
For standard dryer operating conditions, see the following table of
recommended settings:
Model
250
• EXTERNAL - if there is an external drain (24VAC).
To change operation mode, use the parameter d3 (see par. 5.3 in List
of parameters).
Y
Only set the EXTERNAL mode in absence of the solenoid valve.
Otherwise the relative coil could become damaged.
Alarm log
Contains the descriptions of the last alarms (max. 8).
.
é
Press
for 5 seconds: the keypad now operates in Alarm MENU
mode and the events can be scrolled with
Every event is displayed with "ALx" (x=1-8).
AL1 = most recent event.
If there are no events "---" appears.
Parameter d1
5
z
é
and
.
3
250